Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00026 INSP-Final Inspection2/28/20122/28/20122/28/2012 4:54:55 PMPFAIL
Plans do not match installation, number of devices or scope of work completed.
FIR11-00435 INSP-Final Inspection2/28/20122/28/20122/28/2012 4:52:09 PMPPART
Final pending corrections per 430 completed 8/29/11 regarding sync issues.
FIR11-00371 INSP-Final Inspection2/28/20122/28/20122/28/2012 4:49:18 PMPPASS
Fire sprinkler permit finaled. Inspection passed.
BLD11-02870 FIRE-Final Inspection2/28/20122/28/20122/28/2012 4:48:23 PMPNR
Pending ceiling tile installation, address numbers, project related FIR permit final. Exits and EM lights tested okay.
FIR12-00015 INSP-Final Inspection2/28/20122/28/20122/28/2012 4:46:54 PMPNR
BLD11-02020 FIRE-Conference2/28/20122/28/20122/28/2012 4:46:21 PMPDONE
Regarding phasing.
BLD11-02020 FIRE-Final Inspection2/28/20122/28/20122/28/2012 4:45:40 PMAPART
Partial completion- new reception, waiting, consultation, blood draw and nurse station only. Noted one exit sign to be repaired, one a/v to be adjusted.
BLD11-00346 FIRE-Final Inspection2/28/20122/28/20122/28/2012 2:07:52 PMPPASS
Verified previous correction notice items. Fire life safety passed.
FIR11-00555 INSP-Final Inspection2/27/20122/28/20122/28/2012 1:24:36 PMAPASS
Verified installation of the knox box and reciept of record of completion documents. Noted phone line one trouble condition on the panel at the time of inspection- tech in route to repair per conversation with tenant.
FIR11-00578 INSP-Sprinkler Rough-in/Hydro2/27/20122/28/20122/28/2012 1:19:59 PMAPART
UG fire supply line hydrostatic test passed.
FIR11-00680 INSP-Sprinkler Rough-in/Hydro2/27/20122/28/20122/28/2012 1:19:12 PMAFAIL
UG fire supply line hydrostatic test failed due to visible leakage at the 1/2" valve and pressure loss at the guage.
FIR11-00563 INSP-Sprinkler Rough-in/Hydro2/27/20122/28/20122/28/2012 1:17:30 PMAPART
Overhead work at the 3rd floor rooms 321-327 and the library room are approved for ceiling cover. Noted missing expansion joint at the 2" main on grid line 22. See plans for annotations.
FIR11-00527 INSP-Final Inspection2/27/20122/28/20122/28/2012 1:12:41 PMAPART
Fire sprinkler work okay for final when travel caps at pendent heads are removed and two missing escutcheons are installed.