Inspections for the day of: Thursday, February 28, 2013.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00043 INSP-Sprinkler Rough-in2/28/20132/28/20132/28/2013 3:52:04 PMPPART
See the city approved plans for locations in the main shop/service area and detail/carwash areas where corrections are required. The plans need to be re-submitted showing the additional branchline and heads which will effect the remote areas. Branch line restraints and retaining straps are missing in several locations. Pipe clearance at the CMU penatrations are not big enough....ect.
FIR12-00418 FIR-Aging Inspection2/28/20132/28/20132/28/2013 3:25:03 PM NR
Work is in progress
FIR13-00066 INSP-Final Inspection2/28/20132/28/20132/28/2013 3:07:40 PMPPASS
permit finaled
BLD12-00684 FIRE-Final Inspection2/27/20132/28/20132/28/2013 12:59:50 PMAPASS
life safety passed
BLD12-00676 FIRE-Final Inspection2/27/20132/28/20132/28/2013 12:57:32 PMAPASS
life safety passed. Per letter from engineer the duct smoke detector is not required by them. Dead bolt is going to be blanked off.
BLD12-00682 FIRE-Final Inspection2/27/20132/28/20132/28/2013 12:51:12 PMAPASS
Life safety passed
FIR12-00033 INSP-Alarm Testing2/27/20132/28/20132/28/2013 10:06:59 AMADONE
Todays inspection was just for the west corridor outside of Payroll which included two smoke detectors and two ceiling mounted audio/visuals. I was requested to inspect the devices that were changed out inside the Payroll offce but I declined due to this extra work being outside of the approved scope of work as shown on the city approved plans. This extra work needs to be submitted/approved prior to an inspection. I did step into the office and saw that the devices were functioning. I was also requested to verify work on the second floor which again is outside of the approved scope of work. I noted that it appears all of the devices are functioning.