ELE17-00478
| Electrical Rough-In | 2/28/2017 | 2/28/2017 | 2/28/2017 3:19:55 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg 300.15- All wiring shall terminate in a box.Too many old existing conduits and MC cables with loose wiring hanging out. If existing flexible conduit are to remain they shall be supported as per NEC..BLD is for core and shell only, TI has not been issued yet.
|
ELE17-00382
| Electrical Rough-In | 2/28/2017 | 2/28/2017 | 2/28/2017 2:13:22 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL Reception and conderence room grid rough in ok cover
|
ELE17-00501
| Temporary Service | 2/27/2017 | 2/28/2017 | 2/28/2017 12:43:34 PM | A | FAIL |
|
|
overhead temporary power pole Phone #: ###-#### Inspection requested via web by Rick Beckman 230.24(B)- Vertical clearance for overhead service entrance conductors shall be 10' minimum. Pole measures 9 1/2' and drip loop would be lower.
|
ELE16-03933
| Electrical Rough-In | 2/27/2017 | 2/28/2017 | 2/28/2017 12:00:41 PM | A | FAIL |
|
|
Lonny-fire pump Phone #: ###-#### 110.26- Clear work space shall be provided for all electrical equipment in room 113 for fire pump controller. 30" wide or width of equipment and 36" deep with voltage present. Work space shall have a height of 6 1/2' minimum. Clear egress path shall also be provided. Pending additional equipment to be added.
|
ELE17-00498
| Electrical Rough-In | 2/27/2017 | 2/28/2017 | 2/28/2017 10:24:35 AM | A | PASS |
|
|
underground raceway for detached garage Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover
|
ELE17-00499
| Electrical Rough-In | 2/27/2017 | 2/28/2017 | 2/28/2017 10:24:11 AM | A | PASS |
|
|
underground raceway for detached garage Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover
|
ELE17-00500
| Electrical Rough-In | 2/27/2017 | 2/28/2017 | 2/28/2017 10:23:48 AM | A | PASS |
|
|
underground raceway for detached garage Phone #: ###-#### Inspection requested via web by Rowdy Monroe Rough in ok cover
|
ELE17-00479
| Rough-In Permanent Service | 2/27/2017 | 2/28/2017 | 2/28/2017 9:03:33 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|
ELE17-00439
| Rough-In Permanent Service | 2/27/2017 | 2/28/2017 | 2/28/2017 8:53:54 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|