Inspections for the day of: Tuesday, February 28, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-00478 Electrical Rough-In2/28/20172/28/20172/28/2017 3:19:55 PMPFAIL
Phone #: ###-#### Inspection requested via web by jamie berg
300.15- All wiring shall terminate in a box.Too many old existing conduits and MC cables with loose wiring hanging out. If existing flexible conduit are to remain they shall be supported as per NEC..BLD is for core and shell only, TI has not been issued yet.
ELE17-00382 Electrical Rough-In2/28/20172/28/20172/28/2017 2:13:22 PMPPASS
Phone #: ###-#### Inspection requested via web by JENNY EMEL
Reception and conderence room grid rough in ok cover
ELE17-00501 Temporary Service2/27/20172/28/20172/28/2017 12:43:34 PMAFAIL
overhead temporary power pole Phone #: ###-#### Inspection requested via web by Rick Beckman
230.24(B)- Vertical clearance for overhead service entrance conductors shall be 10' minimum. Pole measures 9 1/2' and drip loop would be lower.
ELE16-03933 Electrical Rough-In2/27/20172/28/20172/28/2017 12:00:41 PMAFAIL
Lonny-fire pump Phone #: ###-####
110.26- Clear work space shall be provided for all electrical equipment in room 113 for fire pump controller. 30" wide or width of equipment and 36" deep with voltage present. Work space shall have a height of 6 1/2' minimum. Clear egress path shall also be provided. Pending additional equipment to be added.
ELE17-00498 Electrical Rough-In2/27/20172/28/20172/28/2017 10:24:35 AMAPASS
underground raceway for detached garage Phone #: ###-#### Inspection requested via web by Rowdy Monroe
Rough in ok cover
ELE17-00499 Electrical Rough-In2/27/20172/28/20172/28/2017 10:24:11 AMAPASS
underground raceway for detached garage Phone #: ###-#### Inspection requested via web by Rowdy Monroe
Rough in ok cover
ELE17-00500 Electrical Rough-In2/27/20172/28/20172/28/2017 10:23:48 AMAPASS
underground raceway for detached garage Phone #: ###-#### Inspection requested via web by Rowdy Monroe
Rough in ok cover
ELE17-00479 Rough-In Permanent Service2/27/20172/28/20172/28/2017 9:03:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok
ELE17-00439 Rough-In Permanent Service2/27/20172/28/20172/28/2017 8:53:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Rough in ok cover p/s u/g n ok