FIR16-00797
| INSP-Sprinkler Rough-in/Hydro | 2/27/2017 | 2/28/2017 | 3/1/2017 10:04:01 AM | A | PASS |
|
|
Hdrostatic test for overhead fire sprinkler piping complete
|
BLD15-01116
| FIRE-Final Inspection | 2/28/2017 | 2/28/2017 | 2/28/2017 3:51:13 PM | P | PASS |
|
|
Final fire sprinkler inspection complete, final fire alarm inspection complete, fire extinguishers are mounted with current inspection tags, knox box is in place. Final life fire safety inspection passed/complete.
|
FIR16-00754
| INSP-Final Inspection | 2/27/2017 | 2/28/2017 | 2/28/2017 3:45:58 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR16-00450
| INSP-Final Inspection | 2/28/2017 | 2/28/2017 | 2/28/2017 3:45:23 PM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR16-00511
| INSP-Sprinkler Rough-in/Hydro | 2/28/2017 | 2/28/2017 | 2/28/2017 3:44:48 PM | P | CANC |
|
|
Not ready for inspection, this request is cancelled.
|
FIR16-00512
| INSP-Sprinkler Rough-in/Hydro | 2/28/2017 | 2/28/2017 | 2/28/2017 3:43:56 PM | P | PART |
|
|
Rough to cover inspection complete for overhead fire sprinkler piping, room 102 on level 1 cannt be covered, FDC piping needs hanges installed before cover is allowed. Level 2 approved for cover, partial cover allowed for level 3, piping in attic spaces on level 3 and 4 cannot be covered until tenting is installed, inspected and passed.
|
BLD16-03951
| FIRE-Final Inspection | 2/28/2017 | 2/28/2017 | 2/28/2017 3:39:22 PM | P | PASS |
|
|
Final fire sprinkler inspection complete, final fire alarm inspection complete, final commercial hood fire suppression system inspection complete, fire extinguishers are mounted with current inspection tags, building has a knox box. Final life fire safety inspection passed/complete
|
FIR17-00025
| INSP-Final Inspection | 2/28/2017 | 2/28/2017 | 2/28/2017 3:37:25 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete
|
FIR17-00025
| INSP-Sprinkler Rough-in | 2/27/2017 | 2/28/2017 | 2/28/2017 3:36:50 PM | P | CANC |
|
|
Inspection request is for a final inspection, not a rough in, this inspection request cancelled and a new one will be generated.
|
FIR17-00008
| INSP-Final Inspection | 2/27/2017 | 2/28/2017 | 2/28/2017 3:34:47 PM | P | PASS |
|
|
Final inspection for commercial hood fire suppression system passed/complete.
|
FIR17-00007
| INSP-Final Inspection | 2/27/2017 | 2/28/2017 | 2/28/2017 3:17:29 PM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR16-00573
| INSP-Final Inspection | 2/28/2017 | 2/28/2017 | 2/28/2017 10:11:23 AM | P | CANC |
|
|
|
FIR17-00076
| INSP-Sprinkler Rough-in | 2/27/2017 | 2/28/2017 | 2/28/2017 7:41:53 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, area of work approved for cover.
|
FIR17-00060
| INSP-Sprinkler Rough-in | 2/27/2017 | 2/28/2017 | 2/28/2017 7:13:28 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
|
FIR16-00556
| INSP-Sprinkler Rough-in/Hydro | 2/27/2017 | 2/28/2017 | 2/28/2017 6:51:21 AM | A | PART |
|
|
Tenting inspection for pod 1, level 3 complete, approved for cover.
|