Inspections for the day of: Thursday, February 28, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00642 ELE-Aging Inspection2/28/20192/28/20192/28/2019 3:46:58 PM PASS
Called contact and left message
ELE19-00177 Final2/28/20192/28/20192/28/2019 3:23:57 PMPFAIL
Chad VanOrden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
No ceiling inspection, wireman provided a ladder for spot check. Office furniture not complete. Whips to be removed until can be terminated.
BCC 4-05-32 No code violation to be retained.
330.30- Existing MC installed feeding conference room table is exposed to physical damage and shall be removed, or replace with other approved wiring method.
ELE18-01951 Final2/27/20192/28/20192/28/2019 1:55:53 PMAPART
Final for wild dog/hyena building Phone #: ###-#### Inspection requested via web by Mike McCarrel
Cody Riddle Head of plan review has approved the installation of an electric fence for the wild dog and hiena enclosures as an exeption to BCC 4-05-31(B).
As per 210.8(B)(4)- Outdoor receptacle power supply for electric fence does require GFCI protection. To prevent nuisance tripping creating a dangerous situation for handlers unit would be ok to hardwire with a disconnecting means provided, 110.25 lockout acceptacle.
General contractor to fill in hole in front of panels ASAP as per 240.24(A).
Building D-5 TCO ok
ELE18-02742 Final2/27/20192/28/20192/28/2019 1:43:01 PMAPART
Final for gibbon building Phone #: ###-#### Inspection requested via web by Mike McCarrel To install GFCI devices protecting soffit receptacles in a readily accessible location by final as per 210.8.
General contractor must provide build up of grade in front of panel location ASAP as per 240.24(A).
TCO of building C4 ok
ELE18-03320 Final2/27/20192/28/20192/28/2019 11:31:51 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Janitors closet basement only, refers, ice makers on all floors. Level 5 drinking fountain GFCI,
Level 5 patio GFI in-op,
Inspect level 5 board room grid.
Over stair between level 4 and 5 not complete.
ELE19-00335 Conference2/28/20192/28/20192/28/2019 9:23:05 AMPPASS
Discussed work clearance required for disconnecting means for upstairs mechenical equipment in small room. As per 110.26 minimum width and depth shall be present. As of now 24" width for 2 unfused disconnects.
ELE19-00408 Final2/26/20192/28/20192/28/2019 9:16:28 AMAPASS
Contact:Josh Mangum Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok