ELE16-00642
| ELE-Aging Inspection | 2/28/2019 | 2/28/2019 | 2/28/2019 3:46:58 PM | | PASS |
|
|
Called contact and left message
|
ELE19-00177
| Final | 2/28/2019 | 2/28/2019 | 2/28/2019 3:23:57 PM | P | FAIL |
|
|
Chad VanOrden is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce No ceiling inspection, wireman provided a ladder for spot check. Office furniture not complete. Whips to be removed until can be terminated. BCC 4-05-32 No code violation to be retained. 330.30- Existing MC installed feeding conference room table is exposed to physical damage and shall be removed, or replace with other approved wiring method.
|
ELE18-01951
| Final | 2/27/2019 | 2/28/2019 | 2/28/2019 1:55:53 PM | A | PART |
|
|
Final for wild dog/hyena building Phone #: ###-#### Inspection requested via web by Mike McCarrel Cody Riddle Head of plan review has approved the installation of an electric fence for the wild dog and hiena enclosures as an exeption to BCC 4-05-31(B). As per 210.8(B)(4)- Outdoor receptacle power supply for electric fence does require GFCI protection. To prevent nuisance tripping creating a dangerous situation for handlers unit would be ok to hardwire with a disconnecting means provided, 110.25 lockout acceptacle. General contractor to fill in hole in front of panels ASAP as per 240.24(A). Building D-5 TCO ok
|
ELE18-02742
| Final | 2/27/2019 | 2/28/2019 | 2/28/2019 1:43:01 PM | A | PART |
|
|
Final for gibbon building Phone #: ###-#### Inspection requested via web by Mike McCarrel To install GFCI devices protecting soffit receptacles in a readily accessible location by final as per 210.8. General contractor must provide build up of grade in front of panel location ASAP as per 240.24(A). TCO of building C4 ok
|
ELE18-03320
| Final | 2/27/2019 | 2/28/2019 | 2/28/2019 11:31:51 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 210.8(B)- All receptacle outlets located with in 6' of a sink shall have GFCI protection. Janitors closet basement only, refers, ice makers on all floors. Level 5 drinking fountain GFCI, Level 5 patio GFI in-op, Inspect level 5 board room grid. Over stair between level 4 and 5 not complete.
|
ELE19-00335
| Conference | 2/28/2019 | 2/28/2019 | 2/28/2019 9:23:05 AM | P | PASS |
|
|
Discussed work clearance required for disconnecting means for upstairs mechenical equipment in small room. As per 110.26 minimum width and depth shall be present. As of now 24" width for 2 unfused disconnects.
|
ELE19-00408
| Final | 2/26/2019 | 2/28/2019 | 2/28/2019 9:16:28 AM | A | PASS |
|
|
Contact:Josh Mangum Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok
|