ELE20-00209
| Electrical Rough-In | 2/28/2020 | 2/28/2020 | 2/28/2020 1:48:32 PM | P | PASS |
|
|
Ceiling Inspection Phone #: ###-#### Inspection requested via web by Steven Ragan Grid rough in ok cover
|
ELE20-00707
| Electrical Rough-In | 2/28/2020 | 2/28/2020 | 2/28/2020 1:15:28 PM | P | PASS |
|
|
walls ; hard ceilings Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Discussed panel board bonding as per 517.14 and tamper resistant receptacle locations as per 406.12(5) due to not noted on print. Walls, hardlids, and soffits rough in ok cover.
|
ELE20-00617
| Final | 2/28/2020 | 2/28/2020 | 2/28/2020 1:14:52 PM | P | PASS |
|
|
Correction complete, Final ok
|
ELE20-00617
| Final | 2/25/2020 | 2/28/2020 | 2/28/2020 12:18:47 PM | A | FAIL |
|
|
Mark Phone #: ###-#### 250.28- Main bonding jumper shall be installed as per manufacturers instructions.
|
ELE20-00693
| Final | 2/27/2020 | 2/28/2020 | 2/28/2020 11:31:50 AM | A | FAIL |
|
|
Contact: Brian Gee.... call before going so Brian can meet you there please Phone #: ###-#### Inspection requested via web by Deb Gooden Relocated 2'x4' layin luminaire to for new walls. Park on south side for nearest entrance. 314.23- Boxes shall be secured to structure. Contractor supplied ladder, found boxes hanging on MC cable and EMT conduit. 400.12- Flexible cords shall not be installed above ceiling grid. Game area has receptacle located in ceiling with 2 extension cords plugged and routed above grid to unknown locations.
|
ELE19-04826
| Electrical Rough-In | 2/27/2020 | 2/28/2020 | 2/28/2020 10:49:56 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tom Jenkins North side underground rough in ok cover
|
ELE19-04502
| Electrical Rough-In | 2/28/2020 | 2/28/2020 | 2/28/2020 9:42:19 AM | A | PASS |
|
|
Underground retail and lobby Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Under slab for areas noted rough in ok cover.
|
ELE19-04801
| Final | 2/27/2020 | 2/28/2020 | 2/27/2020 1:16:49 PM | P | PASS |
|
|
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|