FIR19-00933
| INSP-Sprinkler Rough-in | 2/27/2020 | 2/28/2020 | 2/28/2020 3:24:31 PM | P | FAIL |
|
|
Notated city approved drawings with red ink area where upright heads are overspaced,inspection stopped after notation.
Rough in for first floor. Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD18-04075
| FIRE-Final Inspection | 2/27/2020 | 2/28/2020 | 2/28/2020 3:23:24 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguiahers are placed with current inspection tags. Final life fire safety inspection for area of work complete, signature provided on permit sign off card.
electrical inspection is set for pm Phone #: ###-#### Inspection requested via web by chad stradley
|
BLD20-00509
| FIRE-Final Inspection | 2/27/2020 | 2/28/2020 | 2/28/2020 12:37:27 PM | P | FAIL |
|
|
Provide annual inspection on fire extinguisher as discussed. Note number 11 on the review comments requires signage on main entry reading "Door to remain unlocked while building is occupied".
Cory Phone #: ###-####
|
BLD19-03157
| FIRE-Final Inspection | 2/27/2020 | 2/28/2020 | 2/28/2020 11:09:54 AM | A | PASS |
|
|
Previously noted items have been corrected, spoke with Michael Hanson about round type door hardware on the east door as well as exit signage removal. Based on occupant load one exit is required, door hardware on east door will remain. Exit sigange has been removed as well due to not being required. Final life fire safety inspection is complete, signature provided on permit sign off card.
Santiago Phone #: ###-####
|
FIR19-00770
| INSP-Final Inspection | 2/27/2020 | 2/28/2020 | 2/28/2020 10:37:25 AM | A | FAIL |
|
|
Premit is under review as of these notes, final inspection cannot be performed until permit is back into issued status. According to SUEZ, water meter is a 5/8 water meter, not 1 inch as show on city approved documents.
Jon Beazer is the contact for this final inspection. Thank you for your help. Have a good day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-00822
| FIRE-Conference | 2/28/2020 | 2/28/2020 | 2/28/2020 10:35:45 AM | A | DONE |
|
|
Need to verify coverings around screen, could not verify at time of conference. Sprinkler heads will need to be added if obstructions are installed above screen.
|
BLD19-00822
| FIRE-Final Inspection | 2/27/2020 | 2/28/2020 | 2/28/2020 10:33:00 AM | A | CANC |
|
|
Request turned into a conference, this request is cancelled.
tyler Phone #: ###-####
|
FIR19-00468
| INSP-Sprinkler Rough-in/Hydro | 2/27/2020 | 2/28/2020 | 2/28/2020 10:32:10 AM | A | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping on levels 1 and 2 witnessed, no pressure loss observed.
ROY IS OUR FOREMAN Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|