Inspections for the day of: Friday, February 29, 2008.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02128 Final2/29/20082/29/20082/29/2008 3:59:12 PMPPASS
allen Phone #: ###-####
ELE07-02128 Permanent Service2/29/20082/29/20082/29/2008 3:58:59 PMPPASS
p/s u/g new ok
ELE06-01438 Final2/29/20082/29/20082/29/2008 3:37:16 PMPPASS
call Paul 1/2 hr prior to going Phone #: ###-#### ok card signed
ELE07-03876 Final2/29/20082/29/20082/29/2008 2:49:38 PMPPASS
jean Phone #: ###-#### ok
ELE08-00345 Electrical Rough-In2/29/20082/29/20082/29/2008 2:13:31 PMPFAIL
reinspect; Greg Phone #: ###-#### correction not made still needs 11/4" for cables parallel to studs called left message
ELE08-00500 Permanent Service2/29/20082/29/20082/29/2008 1:42:40 PMPCANC
Roy; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt see added r/i
ELE08-00500 Electrical Rough-In2/29/20082/29/20082/29/2008 1:42:19 PMPPART
Roy; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt partial u/g ok
ELE08-00494 Electrical Rough-In2/29/20082/29/20082/29/2008 1:04:32 PMPPASS
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA
walls and ceilings ok
ELE08-00505 Electrical Rough-In2/29/20082/29/20082/29/2008 12:25:05 PMPPART
wall rough-in, cal John Phone #: ###-#### Internet Inspection Request from: John Campbell walls ADA restrms
ELE08-00296 Electrical Rough-In2/28/20082/29/20082/29/2008 10:59:16 AMAPART
Scheduled by a contractor via Hello! on 2/28/2008 at 2:56:38 PM. Contact: ###-####. 1st level of u/g duct banks ok
ELE07-03907 Electrical Rough-In2/28/20082/29/20082/29/2008 10:07:47 AMAPART
Ceiling inspection. St. Mark''s School Addition. Contact is Brian Cornell. Phone #: ###-#### Internet Inspection Request from: Richard Montgomery ok
ELE08-00138 Final2/29/20082/29/20082/29/2008 9:41:25 AMPPASS
Scheduled by a contractor via Hello! on 2/29/2008 at 8:07:01 AM. Contact: (208) ok
ELE08-00200 Final2/29/20082/29/20082/29/2008 9:41:00 AMAPASS
Scheduled by a contractor via Hello! on 2/29/2008 at 5:54:46 AM. Contact: ###-####. ok
ELE08-00345 Electrical Rough-In2/28/20082/29/20082/29/2008 8:30:38 AMAFAIL
craig- call 1st before insp Phone #: ###-#### called left message, corr 300.4 shall provide 11/4" for cables parallel to framing members, B C C shall complete makeup
ELE08-00446 Electrical Rough-In2/28/20082/29/20082/28/2008 3:46:20 PMAFAIL
Phone #: ###-#### corr called300.10&12 tighten all locknuts, 110.3(B) use only manufactures listed breakers, and 20 amp max breaker for a/c, 312.5(C) romex not allowed in concuit, unless done as code noted states, 408.7 seal unused breaker openings