FIR11-00301
| INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 2/29/2012 | 3/1/2012 7:48:24 AM | P | PART |
|
|
Re-inspection for corrections system 8 sub fab include the following locations: added coverage at extended ductwork, over spacing at sub fab mechanical, coverage added at the catwalk and soffits between elevator machine room 001A and communication room 001B.
|
FIR11-00431
| INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 2/29/2012 | 3/1/2012 7:39:43 AM | A | PART |
|
|
Re-inspection for system 2 corrections finished at the following locations: hall 100R including added seismic bracing, hangers, and spacing okayed with the exception of one area at the intersection of the corridors @ 140ft2: west stair 100W okay for cover: TEM labs 104B thru 104D approved for cover, noted cap at 4" grid main in TEM lab 104E terminates inside a sheetrock wall: auxillary drain at the 4" main relocated to the 6" main at link 100A.
|
FIR11-00659
| INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 2/29/2012 | 3/1/2012 7:21:09 AM | A | PART |
|
|
Overhead hydrostatic test and rough-in inspection completed acceptable.
|
FIR11-00550
| INSP-Final Inspection | 2/27/2012 | 2/29/2012 | 3/1/2012 7:18:37 AM | P | PART |
|
|
Completed device testing at all tenant rooms on the 1st thru 5th floors including ADA rooms and notification appliances in common and public areas. Items noted include four HD to be replaced, one tenant denied access for inspection purposes, cd settings at ADA rooms need adjusted. Provide as-built drawings.
|
BLD12-00281
| FIRE-Final Inspection | 2/28/2012 | 2/29/2012 | 2/29/2012 11:09:02 AM | A | PASS |
|
|
Life safety passed on the condition that approved hardware is installed at the back door including removal of the surface bolt, manual thumbturn, door knob and 2x4 crossbar. This to be completed prior to structural final inspection for verification of compliance as discussed with tenant and tenant rep.
|
FIR11-00631
| INSP-Sprinkler Rough-in/Hydro | 2/27/2012 | 2/29/2012 | 2/29/2012 11:03:37 AM | A | CANC |
|
|
Overbooked
|
FIR12-00011
| INSP-Final Inspection | 2/27/2012 | 2/29/2012 | 2/29/2012 11:03:04 AM | A | CANC |
|
|
Overbooked
|
BLD10-02412
| FIRE-Final Inspection | 2/28/2012 | 2/29/2012 | 2/29/2012 10:54:34 AM | A | PASS |
|
|
Structural inspector to verify conditions are met per agreement with contractor and TY.
|
FIR12-00111
| INSP-Sprinkler Rough-in | 2/28/2012 | 2/29/2012 | 2/29/2012 10:46:09 AM | A | PART |
|
|
Overhead modifications at the tenant remodel are approved for drop ceiling cover.
|
BLD11-02870
| FIRE-Final Inspection | 2/28/2012 | 2/29/2012 | 2/29/2012 10:44:20 AM | A | PASS |
|
|
Correction items verified for completion. Fire life safety inspection passed. * NOTE: Per general contractor and fire sprinkler contractor survey, head count in the building remains below 100. Therefore, conditions per the UFC under which the structure was built still apply regarding offsite monitoring.
|
FIR12-00015
| INSP-Final Inspection | 2/28/2012 | 2/29/2012 | 2/29/2012 10:37:43 AM | A | PASS |
|
|
Scope of work passed final walkthrough- missing escutcheon installed while on site. Fire sprinkler permit finaled.
|
FIR11-00448
| INSP-Sprinkler Rough-in/Hydro | 2/28/2012 | 2/29/2012 | 2/28/2012 11:44:52 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|