FIR15-00795
| INSP-Sprinkler Rough-in/Hydro | 2/29/2016 | 2/29/2016 | 2/29/2016 3:13:09 PM | P | FAIL |
|
|
Rough to cover inspection performed, cover is not approved, inspection stopped after finding numorous hangers that are overspaced, hanger spacing needs to be corrected throughout entire building before cover is approved.
|
FIR16-00081
| INSP-Sprinkler Rough-in | 2/29/2016 | 2/29/2016 | 2/29/2016 3:07:02 PM | P | PASS |
|
|
Rough to cover inspection completed, including tenting for fire sprinkler piping located in attic space, complete area of work approved for cover.
|
FIR15-00795
| INSP-Sprinkler Rough-in/Hydro | 2/26/2016 | 2/29/2016 | 2/29/2016 1:34:55 PM | P | PASS |
|
|
Overhead hydrostatic test, 2 hours @ 200psi passed/complete.
|
FIR16-00071
| INSP-Sprinkler Rough-in | 2/29/2016 | 2/29/2016 | 2/29/2016 1:25:17 PM | P | PASS |
|
|
Rough to cover inspection complete for uderground supply, approved for cover.
|
FIR15-00793
| INSP-Supply line flush | 2/28/2016 | 2/29/2016 | 2/29/2016 1:07:17 PM | P | DONE |
|
|
Underground main line flush complete.
|
FIR16-00009
| INSP-Sprinkler Rough-in | 2/29/2016 | 2/29/2016 | 2/29/2016 11:52:22 AM | P | PASS |
|
|
Rough to cover inspection complete for area of work, overhead sprinkler piping approved for cover.
|
FIR15-00793
| INSP-Sprinkler Rough-in/Hydro | 2/28/2016 | 2/29/2016 | 2/29/2016 10:58:47 AM | A | PASS |
|
|
Hydrostatic test, 2 hours @ 200 psi complete for underground supply.
|
BLD15-03078
| FIRE-Final Inspection | 2/26/2016 | 2/29/2016 | 2/29/2016 10:15:23 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers have current inspection tags. Life fire safety inspection passed/complete.
|
FIR15-00765
| INSP-Final Inspection | 2/29/2016 | 2/29/2016 | 2/29/2016 10:13:15 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD15-04417
| FIRE-Conference | 2/26/2016 | 2/29/2016 | 2/29/2016 9:32:06 AM | A | DONE |
|
|
Fire conference complete, electricians will install exit signs per location of approved drawings, contractor will schedule partial life fire safety inspection when complete.
|
FIR15-00865
| INSP-Sprinkler Rough-in/Hydro | 2/24/2016 | 2/29/2016 | 2/29/2016 9:30:28 AM | A | CANC |
|
|
Inspection request cancelled per conversation with Robert, phone number ###-####, contractor will reshcedule hydrostatic test when water is turned on.
|
GRD15-00065
| FIRE-Final Inspection | 2/26/2016 | 2/29/2016 | 2/29/2016 9:05:24 AM | A | PASS |
|
|
Life fire safety inspection passed/complete
|
FIR16-00058
| INSP-Sprinkler Rough-in | 2/26/2016 | 2/29/2016 | 2/29/2016 8:54:58 AM | A | PASS |
|
|
Rough to cover inspection complete for area of work, approved for cover.
|