Inspections for the day of: Monday, February 29, 2016.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00795 INSP-Sprinkler Rough-in/Hydro2/29/20162/29/20162/29/2016 3:13:09 PMPFAIL
Rough to cover inspection performed, cover is not approved, inspection stopped after finding numorous hangers that are overspaced, hanger spacing needs to be corrected throughout entire building before cover is approved.
FIR16-00081 INSP-Sprinkler Rough-in2/29/20162/29/20162/29/2016 3:07:02 PMPPASS
Rough to cover inspection completed, including tenting for fire sprinkler piping located in attic space, complete area of work approved for cover.
FIR15-00795 INSP-Sprinkler Rough-in/Hydro2/26/20162/29/20162/29/2016 1:34:55 PMPPASS
Overhead hydrostatic test, 2 hours @ 200psi passed/complete.
FIR16-00071 INSP-Sprinkler Rough-in2/29/20162/29/20162/29/2016 1:25:17 PMPPASS
Rough to cover inspection complete for uderground supply, approved for cover.
FIR15-00793 INSP-Supply line flush2/28/20162/29/20162/29/2016 1:07:17 PMPDONE
Underground main line flush complete.
FIR16-00009 INSP-Sprinkler Rough-in2/29/20162/29/20162/29/2016 11:52:22 AMPPASS
Rough to cover inspection complete for area of work, overhead sprinkler piping approved for cover.
FIR15-00793 INSP-Sprinkler Rough-in/Hydro2/28/20162/29/20162/29/2016 10:58:47 AMAPASS
Hydrostatic test, 2 hours @ 200 psi complete for underground supply.
BLD15-03078 FIRE-Final Inspection2/26/20162/29/20162/29/2016 10:15:23 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers have current inspection tags. Life fire safety inspection passed/complete.
FIR15-00765 INSP-Final Inspection2/29/20162/29/20162/29/2016 10:13:15 AMAPASS
Final fire alarm inspection passed/complete
BLD15-04417 FIRE-Conference2/26/20162/29/20162/29/2016 9:32:06 AMADONE
Fire conference complete, electricians will install exit signs per location of approved drawings, contractor will schedule partial life fire safety inspection when complete.
FIR15-00865 INSP-Sprinkler Rough-in/Hydro2/24/20162/29/20162/29/2016 9:30:28 AMACANC
Inspection request cancelled per conversation with Robert, phone number ###-####, contractor will reshcedule hydrostatic test when water is turned on.
GRD15-00065 FIRE-Final Inspection2/26/20162/29/20162/29/2016 9:05:24 AMAPASS
Life fire safety inspection passed/complete
FIR16-00058 INSP-Sprinkler Rough-in2/26/20162/29/20162/29/2016 8:54:58 AMAPASS
Rough to cover inspection complete for area of work, approved for cover.