Inspections for the day of: Tuesday, February 3, 2004.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-01695 FIRE-Conference2/3/20042/3/20042/3/2004 12:00:00 AMAPART
sprinkler piping on the north and south sides of the 2nd floor beams is ok to cover 2/3/2004 10:20:53 AM
BLD01-03114 FIRE-Final Inspection2/3/20042/3/20042/3/2004 12:00:00 AMPFAIL
Provide exit light at rear door of bar and emergency light per plans. Provide occupant load signs. Provide "knox" key box. Fire alarm system is not code compliant. There appears to be no smoke, pull or horn. Owner did not know of any locations they might be. Provide verification of review note #32 with is the hvac shut down requirements 2/4/2004 8:00:49 AM
BLD01-03115 FIRE-Final Inspection2/3/20042/3/20042/3/2004 12:00:00 AMPPASS
life safety finaled 2/3/2004 4:37:30 PM
FIR03-00764 INSP-Final Inspection2/3/20042/3/20042/3/2004 12:00:00 AMPFAIL
Upright sprinkler heads are overspaced on the Bangkok Thialand side of the common wall. Pendant heads are 8' off of the restroom walls in the dining area. Pendant head in the scullery (service area) exceeds the 130 max spacing. The area is to be considered ordinary group 1. I could not verify if the hangers were attached as requested to the top chord 2/3/2004 2:44:41 PM
FIR03-00570 INSP-Final Inspection2/3/20042/3/20042/3/2004 12:00:00 AMPFAIL
Their are no approved plans on site. 2/3/2004 1:56:26 PM
BLD03-01135 FIRE-Conference2/3/20042/3/20042/3/2004 12:00:00 AMPDONE
Fire life safety items are ok when the fire sprinklers and fire alarm are finaled