Inspections for the day of: Thursday, February 3, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03856 Final2/2/20052/3/20052/3/2005 12:00:00 AMAPASS
glenn- ###-#### ok to final 2/3/2005 9:07:00 AM
ELE05-00338 Permanent Service2/2/20052/3/20052/3/2005 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/2/2005 at 11:32:36 AM. Contact: ###-####. 110.26 (F) there shall be no foreign pipes above the dedicated equipment space. 2/3/2005 10:26:54 AM
ELE05-00343 Permanent Service2/2/20052/3/20052/3/2005 12:00:00 AMACANC
Lindy; Phone #: ###-#### Internet Inspection Request from: Jan Rice Talked to owner and told them that elect set a time in the pm and will co-ordinate access to house. will cancel this request. 2/2/2005 3:16:39 PM
ELE04-00421 Temporary Service2/2/20052/3/20052/3/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 2/2/2005 at 1:48:32 PM. Contact: ###-####. corrections made. t/s o/h n ok 2/3/2005 9:22:01 AM
ELE05-00335 Electrical Rough-In2/2/20052/3/20052/3/2005 12:00:00 AMAFAIL
Dennis; Phone #: ###-#### Internet Inspection Request from: Jan Rice Bcc all wires shall be made up in boxes,314.17 nm cable shall be stapled within 8" of box. 2/3/2005 8:49:51 AM
ELE05-00353 Electrical Rough-In2/2/20052/3/20052/3/2005 12:00:00 AMACANC
Shaun; Phone #: ###-#### Internet Inspection Request from: Jan Rice Called contractor, No job id, no plans, no address, told him to recall when ready so we are at right place. 2/3/2005 8:09:07 AM
ELE04-01991 Final2/3/20052/3/20052/3/2005 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/3/2005 at 7:58:15 AM. Contact: ###-####. 350.30(A) liquid-tite shall be supported within 3' of box, 358.30 emt shall be strapped within 3' of box, 358.26 there shall not be more than 360 degree in conduit bends, 110.12(A) unused openings shall be closed in panel, 408.4 Panels shall have circuit directory, 110.13(A) equipment (recpts) shall be secured to surface. Called contr and left correction notice. 2/3/2005 2:38:34 PM
ELE04-03006 Conference2/3/20052/3/20052/3/2005 12:00:00 AMPDONE
Please call at least a half hour prior to inpsection///tom; Phone #: ###-#### Internet Inspection Request from: Barbara Moore 2/3/2005 1:10:03 PM met with elect to discuss using gutter at service, not wireway. He will change . 2/3/2005 1:30:31 PM
ELE05-00325 Temporary Service2/3/20052/3/20052/3/2005 12:00:00 AMPPASS
Internet Inspection Request from: Bob Glenn called contr to drive in gnd rod. t/s u/g n ok 2/3/2005 8:36:22 PM
ELE05-00362 Temporary Service2/3/20052/3/20052/3/2005 12:00:00 AMPPASS
mountain valley elect ###-#### t/s u/g n ok 2/3/2005 3:22:40 PM
ELE05-00363 Temporary Service2/3/20052/3/20052/3/2005 12:00:00 AMPFAIL
mountain valley elect ###-#### 250.24(A)(4) enclosure shall not be used as bond, Ground rod needs driven in. CALLED CONTR AND LEFT MESSAGE. 2/3/2005 3:16:23 PM
ELE05-00343 Permanent Service2/2/20052/3/20052/3/2005 12:00:00 AMPPASS
need inspection on 100 amp service, please call andy at ###-#### to set up time so you can be let in. Internet Inspection Request from: Andy Rose met elect, had him add gnd bushing to panel. 2/3/2005 1:33:29 PM