Inspections for the day of: Friday, February 3, 2006.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00312 INSP-Final Inspection2/2/20062/3/20062/3/2006 4:49:04 PMPFAIL
Provide approved hangers for th 4" main. Provide correct attachment for the eq bracing. Provide forward flush. Provide review comments. Provide correct air compressor and air maintenance device.
FIR06-00055 INSP-Alarm Testing2/3/20062/3/20062/3/2006 4:46:19 PMPPART
Need atleast 10.25AH batteries for the facp. Need to test duct detectors and elevator recall. Need nfpa 72 forms and copy of signals.
FIR05-00835 INSP-Final Inspection2/2/20062/3/20062/3/2006 1:40:51 PMPPASS
Permit finaled.
MIS05-00233 FIR-Final1/30/20062/3/20062/3/2006 1:20:58 PMPPASS
Permit finaled
MIS06-00015 FIR-Final1/31/20062/3/20062/3/2006 11:06:40 AMACANC
Shaun, ###-####
FIR05-00897 INSP-Final Inspection1/31/20062/3/20062/3/2006 10:35:48 AMAPASS
Permit finaled
BLD05-02498 FIRE-Final Inspection2/2/20062/3/20062/3/2006 9:03:56 AMAFAIL
Mount fire extinguisher as discussed in the first floor tenant and provide an additional fire extinguisher in the basement lobby. The two exterior lobby exits are allowed to have the keyed hardware, indicators and stickers. All of the other doors for the new tenant as shown on theplans are required to have approved hardware such as lever, pad or crash bar.