FIR05-00312
| INSP-Final Inspection | 2/2/2006 | 2/3/2006 | 2/3/2006 4:49:04 PM | P | FAIL |
|
|
Provide approved hangers for th 4" main. Provide correct attachment for the eq bracing. Provide forward flush. Provide review comments. Provide correct air compressor and air maintenance device.
|
FIR06-00055
| INSP-Alarm Testing | 2/3/2006 | 2/3/2006 | 2/3/2006 4:46:19 PM | P | PART |
|
|
Need atleast 10.25AH batteries for the facp. Need to test duct detectors and elevator recall. Need nfpa 72 forms and copy of signals.
|
FIR05-00835
| INSP-Final Inspection | 2/2/2006 | 2/3/2006 | 2/3/2006 1:40:51 PM | P | PASS |
|
|
Permit finaled.
|
MIS05-00233
| FIR-Final | 1/30/2006 | 2/3/2006 | 2/3/2006 1:20:58 PM | P | PASS |
|
|
Permit finaled
|
MIS06-00015
| FIR-Final | 1/31/2006 | 2/3/2006 | 2/3/2006 11:06:40 AM | A | CANC |
|
|
Shaun, ###-####
|
FIR05-00897
| INSP-Final Inspection | 1/31/2006 | 2/3/2006 | 2/3/2006 10:35:48 AM | A | PASS |
|
|
Permit finaled
|
BLD05-02498
| FIRE-Final Inspection | 2/2/2006 | 2/3/2006 | 2/3/2006 9:03:56 AM | A | FAIL |
|
|
Mount fire extinguisher as discussed in the first floor tenant and provide an additional fire extinguisher in the basement lobby. The two exterior lobby exits are allowed to have the keyed hardware, indicators and stickers. All of the other doors for the new tenant as shown on theplans are required to have approved hardware such as lever, pad or crash bar.
|