BLD08-02487
| FIRE-Final Inspection | 2/3/2009 | 2/3/2009 | 2/3/2009 5:00:31 PM | P | FAIL |
|
|
This inspection was for the first and second floor restrooms. Sprinkler modifications are required due to existing sprinkler heads being located too far from the ceiling and possibly obstructed by duct work and soffits. One sprinkler upright has been painted.. Life safety will be ok in the first and second floor restrooms once a sprinkler permit is issued, inspected and passed.
|
BLD08-02510
| FIRE-Final Inspection | 2/3/2009 | 2/3/2009 | 2/3/2009 4:58:17 PM | P | FAIL |
|
|
Sprinkler modifications are required due to overspaced pendant heads. Life safety will be ok to pass once a sprinkler permit is issued, inspected and passed.
|
FIR08-00616
| INSP-Sprinkler Rough-in/Hydro | 2/3/2009 | 2/3/2009 | 2/3/2009 3:15:36 PM | P | PART |
|
|
See the city approved resubmitted plans for the locations where the sprinkler piping can be covered. I requested a set of as-builts showing the actual piping arrangement on the north end of the remodeling work.
|
FIR08-00757
| INSP-Final Inspection | 2/2/2009 | 2/3/2009 | 2/3/2009 3:13:51 PM | A | FAIL |
|
|
Provide print out of todays signal report, test the duct smoke detectors, provide verification of review comment #20, provide verification of sprinkler coverage at the top of the elevator shaft, provide automatic disconnect and monitoring of the 120 volt power as per review note #6, provide firemans hat functions, recall and shunt trip functions as per 6.16.3, provide as builts showing the additional devices, relocate the smoke and heat detectors to the deck, repair the PIV tamper switch.
|
FIR08-00341
| INSP-Final Inspection | 2/3/2009 | 2/3/2009 | 2/3/2009 2:39:21 PM | P | PASS |
|
|
Permit finaled. A tree was removed from infront of the strobe in the employee breakroom.
|