Inspections for the day of: Thursday, February 3, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00186 Final2/3/20112/3/20112/3/2011 3:04:22 PMPCANC
final Phone #: ###-#### >> Inspection requested via web by Tyler Bowen called and explained that the paper work for the field evaluation for the antenna package shall be received prior to inspection
ESC10-00889 General Inspection2/3/20112/3/20112/3/2011 2:18:15 PMPPASS
looked ok
ELE10-02847 Final2/3/20112/3/20112/3/2011 1:37:15 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Zane Robertson called, left correction notice, NEC 725.5 shall remove abandoned lv cables, 314.23 shall support boxes, 300.11 shall secure boxes, cables,raceways, grid shall not support boxes or cables, 110.12(A) shall close unused openings, BCC shall call for ceiling inspection, no violations shall be retained
ELE11-00203 Final2/3/20112/3/20112/3/2011 12:56:24 PMPPASS
Final on service replacement. Jared ###-#### Phone #: ###-#### >> Inspection requested via web by Randy Fletcher called, ok final
GCE11-00016 GCE-Permanent Service2/2/20112/3/20112/3/2011 10:00:49 AMAPASS
Perm ServiceContractor @ ###-#### p/s o/h rec ok
GCE11-00013 GCE-Rough-In2/2/20112/3/20112/3/2011 9:42:31 AMAPASS
Rough-InTracy @ ###-#### called, ri ok, check outlet in south bedroom at final
GCE11-00013 GCE-Permanent Service2/3/20112/3/20112/3/2011 9:21:30 AMAPASS
Rough-InTracy @ ###-#### p/s o/h rec ok, check guy kit at final
GCE11-00018 GCE-Rough-In2/2/20112/3/20112/3/2011 9:19:28 AMAFAIL
Scope: Rough-In Groundworkcontact: Neil @ ###-#### called, too many bends in conduit, no spacing maintained, no bedding provided, depth too shallow
ELE11-00195 Temporary Service2/2/20112/3/20112/3/2011 8:32:01 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey t/s u/g n ok
ELE11-00187 Rough-In Permanent Service2/3/20112/3/20112/3/2011 8:17:48 AMAPASS
call Dene with any questions.
Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ri ok, p/s u/g n ok
ELE10-01617 ELE-Aging Inspection2/3/20112/3/20112/3/2011 6:14:04 AM DONE
garage not called in, still under construction