Inspections for the day of: Monday, February 3, 2014.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00640 INSP-Final Inspection2/3/20142/3/20142/3/2014 5:07:36 PMPPASS
After hours testing and inspection completed and passed per C. Hanson.
FIR13-00504 INSP-Final Inspection2/3/20142/3/20142/3/2014 5:06:21 PMPPASS
C/N items verified. Final walkthrough passed. Fire sprinkler permit finaled.
FIR13-00524 INSP-Sprinkler Rough-in2/3/20142/3/20142/3/2014 5:05:25 PMPFAIL
Approved plans indicate a max. spacing of 16x16- Noted five locations overspaced at 9' from adjacent walls. Also need to verify materials in contact with CPVC piping are compatible per the mfg. listing such as fire caulk, duct mastic, and cables.
BLD12-01001 FIRE-Conference2/3/20142/3/20142/3/2014 2:50:17 PMPDONE
On site conference regarding project related fire alarm and sprinkler work, fire code review note items, project schedule, smoke alarm locations, etc.
BLD13-03604 FIRE-Final Inspection1/31/20142/3/20142/3/2014 2:46:56 PMANR
Need plan review of revised floorplan prior to field inspection.
BLD13-03205 FIRE-Final Inspection2/3/20142/3/20142/3/2014 2:44:29 PMPPASS
Fire life safety final approved.
FIR12-00639 INSP-Sprinkler Rough-in/Hydro2/3/20142/3/20142/3/2014 1:09:16 PMAPART
OH hydrostatic test of the wet system completed and passed.
FIR12-00639 INSP-Sprinkler Rough-in/Hydro2/3/20142/3/20142/3/2014 1:07:06 PMAPART
OH hydrostatic test of the new dry system passed.
BLD13-02547 FIRE-Final Inspection1/31/20142/3/20142/3/2014 12:00:07 PMAPASS
"Wave four" completed. Final walkthrough passed. Fire life safety finaled.
FIR13-00585 INSP-Final Inspection1/30/20142/3/20142/3/2014 11:57:05 AMAPASS
Previous correction items completed. Functional testing passed. Fire alarm permit finaled.