ELE15-00277
| Temporary Service | 2/3/2015 | 2/3/2015 | 2/3/2015 3:03:58 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn This temp pole already has a meter in it? no previous permit. TS, UG, N, OK
|
ELE15-00275
| Temporary Service | 2/3/2015 | 2/3/2015 | 2/3/2015 3:03:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn TS, UG, N, OK
|
ELE14-01588
| Final | 2/3/2015 | 2/3/2015 | 2/3/2015 2:47:28 PM | P | FAIL |
|
|
Garage code 6314 Phone #: ###-#### Inspection requested via web by Therrin Robertson 422.11 E 1 Overcurrent protection shall not exceed appliance nameplate rating, called Therrin
|
ELE14-01914
| Final | 2/3/2015 | 2/3/2015 | 2/3/2015 2:47:02 PM | P | FAIL |
|
|
Garage code 6314 Phone #: ###-#### Inspection requested via web by Therrin Robertson 422.11 E 1 Overcurrent protection shall not exceed appliance nameplate rating, called Therrin
|
ELE14-03502
| Rough-In Permanent Service | 2/3/2015 | 2/3/2015 | 2/3/2015 2:07:33 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson RI OK PS, UG, N, OK
|
ELE15-00204
| Final | 2/3/2015 | 2/3/2015 | 2/3/2015 1:51:17 PM | P | FAIL |
|
|
If you have any questions, please call Clay ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 110.12A unused openings to be closed 250.94 Intersystem bonding termination required for other systems
Reconnect existing ground conductors to the intersystem bonding termination Called Clay
|
ELE15-00276
| Final | 2/3/2015 | 2/3/2015 | 2/3/2015 1:15:52 PM | P | PASS |
|
|
Please call prior to inspection so we can have someone there to open up Thank you Phone #: ###-#### Inspection requested via web by kendall bender Final OK per Daryl DeGrange
|
ELE15-00276
| Electrical Rough-In | 2/3/2015 | 2/3/2015 | 2/3/2015 1:15:26 PM | P | PASS |
|
|
Please call prior to inspection so we can have someone there to open up Thank you Phone #: ###-#### Inspection requested via web by kendall bender no rough inspection perfromed on floor heat prior to cover, Schluter Ditra Heat cables viewed in thermostat box with sticker and listing still intact
|
ELE14-03298
| Final | 2/3/2015 | 2/3/2015 | 2/3/2015 1:14:08 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender see permit ele15-00276 for floor heat, corrections made final OK
|
ELE15-00274
| Permanent Service | 2/3/2015 | 2/3/2015 | 2/3/2015 12:55:58 PM | P | CANC |
|
|
replaced 100amp panel, will be ready late afternoon, any questions call Fred @###-#### Phone #: ###-#### Inspection requested via web by Andy Rose wrong inspection type
|
ELE15-00274
| Final | 2/3/2015 | 2/3/2015 | 2/3/2015 12:55:31 PM | P | PASS |
|
|
replaced 100amp panel, will be ready late afternoon, any questions call Fred @###-#### Phone #: ###-#### Inspection requested via web by Andy Rose Final OK
|
ELE15-00274
| Electrical Rough-In | 2/3/2015 | 2/3/2015 | 2/3/2015 12:54:56 PM | P | PASS |
|
|
replaced 100amp panel, will be ready late afternoon, any questions call Fred @###-#### Phone #: ###-#### Inspection requested via web by Andy Rose Changed fuse panel to breaker panel RI OK
|
ELE13-02994
| Final | 1/30/2015 | 2/3/2015 | 2/3/2015 12:31:04 PM | P | FAIL |
|
|
Lori Phone #: ###-#### 406.12 A Dwelling unit, tamper resistant receptacles required
|
ELE14-03293
| Electrical Rough-In | 2/3/2015 | 2/3/2015 | 2/3/2015 11:55:49 AM | P | PASS |
|
|
Trench inspection Phone #: ###-#### Inspection requested via web by steve sellers conduit in trench, ok to cover
|
ELE15-00259
| Permanent Service | 2/3/2015 | 2/3/2015 | 2/3/2015 11:44:54 AM | P | PASS |
|
|
We will need to get IPC to re-connect to the new meter panel.
Right after lunch would be good.
Thanks
Mike Phone #: ###-#### Inspection requested via web by Mike Cole PS, OH, N< OK, underground ok from house to garage
|
ELE15-00124
| Electrical Rough-In | 2/2/2015 | 2/3/2015 | 2/3/2015 11:02:59 AM | A | PASS |
|
|
Jose// 14th floor Phone #: ###-#### Walls OK to cover 14th floor, grounds checked and ok for walls 15th floor
|
GCE14-00208
| GCE-Final | 2/2/2015 | 2/3/2015 | 2/3/2015 10:11:27 AM | A | PASS |
|
|
###-#### final ok
|
ELE12-02695
| Final | 1/16/2015 | 2/3/2015 | 2/3/2015 9:35:55 AM | A | PASS |
|
|
Chistian Phone #: ###-#### conduit was placed in ground, wiring was never installed. Owner has no intention to change service from overhead and will open new permit should any work commence from now.
|
ELE15-00076
| Final | 2/2/2015 | 2/3/2015 | 2/3/2015 9:21:43 AM | A | PASS |
|
|
Please call Zac for access at ###-####. He will unlock. Thank you. Phone #: ###-#### Inspection requested via web by Paula Gratiot Final OK
|
ELE15-00265
| Electrical Rough-In | 2/2/2015 | 2/3/2015 | 2/3/2015 9:07:50 AM | A | CANC |
|
|
wall inspection Phone #: ###-#### Inspection requested via web by Seth Stears called contractor, he cancelled this inspection, building contains 5 exam room, 1 injection room, thearpy room and recovery room.
|
ELE14-02895
| Final | 2/2/2015 | 2/3/2015 | 2/2/2015 3:09:18 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Chris Chesnut Final OK
|