Inspections for the day of: Tuesday, February 3, 2015.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00277 Temporary Service2/3/20152/3/20152/3/2015 3:03:58 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
This temp pole already has a meter in it? no previous permit.
TS, UG, N, OK
ELE15-00275 Temporary Service2/3/20152/3/20152/3/2015 3:03:13 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
TS, UG, N, OK
ELE14-01588 Final2/3/20152/3/20152/3/2015 2:47:28 PMPFAIL
Garage code 6314 Phone #: ###-#### Inspection requested via web by Therrin Robertson
422.11 E 1 Overcurrent protection shall not exceed appliance nameplate rating,
called Therrin
ELE14-01914 Final2/3/20152/3/20152/3/2015 2:47:02 PMPFAIL
Garage code 6314 Phone #: ###-#### Inspection requested via web by Therrin Robertson
422.11 E 1 Overcurrent protection shall not exceed appliance nameplate rating,
called Therrin
ELE14-03502 Rough-In Permanent Service2/3/20152/3/20152/3/2015 2:07:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Zane Robertson
RI OK PS, UG, N, OK
ELE15-00204 Final2/3/20152/3/20152/3/2015 1:51:17 PMPFAIL
If you have any questions, please call Clay ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan
110.12A unused openings to be closed
250.94 Intersystem bonding termination required for other systems

Reconnect existing ground conductors to the intersystem bonding termination
Called Clay
ELE15-00276 Final2/3/20152/3/20152/3/2015 1:15:52 PMPPASS
Please call prior to inspection so we can have someone there to open up
Thank you Phone #: ###-#### Inspection requested via web by kendall bender
Final OK per Daryl DeGrange
ELE15-00276 Electrical Rough-In2/3/20152/3/20152/3/2015 1:15:26 PMPPASS
Please call prior to inspection so we can have someone there to open up
Thank you Phone #: ###-#### Inspection requested via web by kendall bender
no rough inspection perfromed on floor heat prior to cover, Schluter Ditra Heat cables viewed in thermostat box with sticker and listing still intact
ELE14-03298 Final2/3/20152/3/20152/3/2015 1:14:08 PMPPASS
Phone #: ###-#### Inspection requested via web by kendall bender
see permit ele15-00276 for floor heat,
corrections made final OK
ELE15-00274 Permanent Service2/3/20152/3/20152/3/2015 12:55:58 PMPCANC
replaced 100amp panel, will be ready late afternoon, any questions call Fred @###-#### Phone #: ###-#### Inspection requested via web by Andy Rose wrong inspection type
ELE15-00274 Final2/3/20152/3/20152/3/2015 12:55:31 PMPPASS
replaced 100amp panel, will be ready late afternoon, any questions call Fred @###-#### Phone #: ###-#### Inspection requested via web by Andy Rose
Final OK
ELE15-00274 Electrical Rough-In2/3/20152/3/20152/3/2015 12:54:56 PMPPASS
replaced 100amp panel, will be ready late afternoon, any questions call Fred @###-#### Phone #: ###-#### Inspection requested via web by Andy Rose
Changed fuse panel to breaker panel RI OK
ELE13-02994 Final1/30/20152/3/20152/3/2015 12:31:04 PMPFAIL
Lori Phone #: ###-####
406.12 A Dwelling unit, tamper resistant receptacles required
ELE14-03293 Electrical Rough-In2/3/20152/3/20152/3/2015 11:55:49 AMPPASS
Trench inspection Phone #: ###-#### Inspection requested via web by steve sellers
conduit in trench, ok to cover
ELE15-00259 Permanent Service2/3/20152/3/20152/3/2015 11:44:54 AMPPASS
We will need to get IPC to re-connect to the new meter panel.

Right after lunch would be good.

Thanks

Mike Phone #: ###-#### Inspection requested via web by Mike Cole
PS, OH, N< OK, underground ok from house to garage
ELE15-00124 Electrical Rough-In2/2/20152/3/20152/3/2015 11:02:59 AMAPASS
Jose// 14th floor Phone #: ###-####
Walls OK to cover 14th floor, grounds checked and ok for walls 15th floor
GCE14-00208 GCE-Final2/2/20152/3/20152/3/2015 10:11:27 AMAPASS
###-####
final ok
ELE12-02695 Final1/16/20152/3/20152/3/2015 9:35:55 AMAPASS
Chistian Phone #: ###-####
conduit was placed in ground, wiring was never installed. Owner has no intention to change service from overhead and will open new permit should any work commence from now.
ELE15-00076 Final2/2/20152/3/20152/3/2015 9:21:43 AMAPASS
Please call Zac for access at ###-####. He will unlock. Thank you. Phone #: ###-#### Inspection requested via web by Paula Gratiot
Final OK
ELE15-00265 Electrical Rough-In2/2/20152/3/20152/3/2015 9:07:50 AMACANC
wall inspection Phone #: ###-#### Inspection requested via web by Seth Stears
called contractor, he cancelled this inspection, building contains 5 exam room, 1 injection room, thearpy room and recovery room.
ELE14-02895 Final2/2/20152/3/20152/2/2015 3:09:18 PMAPASS
Phone #: ###-#### Inspection requested via web by Chris Chesnut
Final OK