ELE13-01329
| ELE-Aging Inspection | 2/3/2017 | 2/3/2017 | 2/8/2017 3:19:46 PM | | PASS |
|
|
Drove by, permits and stickers from 2012, and 2013 still posted in windows. Will watch this job for activity.
|
ELE16-04017
| Electrical Rough-In | 2/3/2017 | 2/3/2017 | 2/3/2017 2:58:46 PM | P | NR |
|
|
Rough In underground, George Morris is contact, ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Used for conference. Discussed if ENT could be encased in concrete and if fittings could be glued. NEC 362.10 states ENT is permitted in concrete and fittings shall be listed and installed as per manufactures instructions for that application. Future inspections if not ready for time requested will have re-inspection fee assessed.
|
ELE17-00037
| Final | 2/3/2017 | 2/3/2017 | 2/3/2017 2:13:42 PM | P | PART |
|
|
Final Inspection for Building #1 Contact Cesar Salcedo Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek TCO for building 1 ok
|
ELE16-02671
| Final | 2/2/2017 | 2/3/2017 | 2/3/2017 11:15:44 AM | A | PASS |
|
|
Replace the existing pylon display with a new monument display. Phone #: ###-#### Inspection requested via web by Ken Olsen corrections made. Final ok
|
ELE17-00037
| Final | 1/31/2017 | 2/3/2017 | 2/3/2017 11:10:36 AM | A | FAIL |
|
|
Final Inspection for Building #1 AM Inspection preferred Contact Cesar Salcedo Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 210.8- All 15 or 20 amp receptacle outlets located within 6' of a sink shall have GFCI protection. All units. 406.12- All 15 and 20 amp receptacle outlets shall be tamper resistant type. Receptacle built into stair light. 124. 422.30- A means shall be provided to disconnect water heater power shall be within sight of unit. 110.25- lockout acceptable.
|
ELE17-00257
| Electrical Rough-In | 2/2/2017 | 2/3/2017 | 2/3/2017 10:08:56 AM | A | PASS |
|
|
Electrician David Forbes ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Wall rough in ok cover
|
ELE16-04041
| Final | 2/2/2017 | 2/3/2017 | 2/3/2017 9:27:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Wires in out soffit are for an existing low volt fixture that will remount when complete. no box or permit required for this voltage. Final ok
|