Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01329 ELE-Aging Inspection2/3/20172/3/20172/8/2017 3:19:46 PM PASS
Drove by, permits and stickers from 2012, and 2013 still posted in windows. Will watch this job for activity.
ELE16-04017 Electrical Rough-In2/3/20172/3/20172/3/2017 2:58:46 PMPNR
Rough In underground, George Morris is contact, ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Used for conference. Discussed if ENT could be encased in concrete and if fittings could be glued. NEC 362.10 states ENT is permitted in concrete and fittings shall be listed and installed as per manufactures instructions for that application.
Future inspections if not ready for time requested will have re-inspection fee assessed.
ELE17-00037 Final2/3/20172/3/20172/3/2017 2:13:42 PMPPART
Final Inspection for Building #1
Contact Cesar Salcedo
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
TCO for building 1 ok
ELE16-02671 Final2/2/20172/3/20172/3/2017 11:15:44 AMAPASS
Replace the existing pylon display with a new monument display. Phone #: ###-#### Inspection requested via web by Ken Olsen corrections made. Final ok
ELE17-00037 Final1/31/20172/3/20172/3/2017 11:10:36 AMAFAIL
Final Inspection for Building #1
AM Inspection preferred
Contact Cesar Salcedo
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
210.8- All 15 or 20 amp receptacle outlets located within 6' of a sink shall have GFCI protection. All units.
406.12- All 15 and 20 amp receptacle outlets shall be tamper resistant type. Receptacle built into stair light. 124.
422.30- A means shall be provided to disconnect water heater power shall be within sight of unit. 110.25- lockout acceptable.
ELE17-00257 Electrical Rough-In2/2/20172/3/20172/3/2017 10:08:56 AMAPASS
Electrician David Forbes ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
Wall rough in ok cover
ELE16-04041 Final2/2/20172/3/20172/3/2017 9:27:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Wires in out soffit are for an existing low volt fixture that will remount when complete. no box or permit required for this voltage. Final ok