Inspections for the day of: Monday, February 3, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-02753 FIRE-Final Inspection2/3/20202/3/20202/3/2020 1:54:31 PMPFAIL
Notated city approved drawings with red ink areas where exit signage was shown as new but is not placed, exit signs shown as wall mounts that are pendant style and exit signs that were shown as existing but were not in place. Provide signage on door for anti-freeze sprinkler riser control valves. Provide fire sprinklers under duct work that exceeds 48 inches. Permit for racking, BLD18-02859 needs to be finaled before life fire safety can be signed off.

Jeff Phone #: ###-####
BLD19-04549 FIRE-Final Inspection2/3/20202/3/20202/3/2020 11:08:24 AMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher are placed with current inspection tag. Final life fire safety inspection is complete, signature provided on permit sign off card.

Bill- inspection for 11th floor Phone #: ###-####
BLD19-04548 FIRE-Final Inspection2/3/20202/3/20202/3/2020 11:08:07 AMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher are placed with current inspection tag. Final life fire safety inspection is complete, signature provided on permit sign off card.

Bill- inspection for 1st floor Phone #: ###-####
GRD19-00045 FIRE-Final Inspection1/31/20202/3/20202/3/2020 11:06:42 AMPCANC
No signature required for life fire safety as noted in permit details, this request is cancelled.

Phone #: ###-#### Inspection requested via web by Stephen Griswold
BLD19-04224 FIRE-Final Inspection1/31/20202/3/20202/3/2020 8:01:33 AMAFAIL
Reference notes entered under FIR19-00932, life fire safety inspection cannot be signed off until FIR permit is finaled, as of this entry as-builts have not been submitted.

John- please call 30 min prior Phone #: ###-####
FIR19-00934 INSP-Final Inspection1/31/20202/3/20202/3/2020 7:34:05 AMAFAIL
Speaker strobe in kitchen area is overspaced. A/V device wiring in seating area is attached to fire sprinkler piping, not allowed to attach to sprinkler piping per NFPA13. Three A/V devices in tenant space experience a double flash during active alarm, troubleshoot double flash issue and repair, A/V devices will be required to be activated during next inspection.

Brian Phone #: ###-####