BLD18-02753
| FIRE-Final Inspection | 2/3/2020 | 2/3/2020 | 2/3/2020 1:54:31 PM | P | FAIL |
|
|
Notated city approved drawings with red ink areas where exit signage was shown as new but is not placed, exit signs shown as wall mounts that are pendant style and exit signs that were shown as existing but were not in place. Provide signage on door for anti-freeze sprinkler riser control valves. Provide fire sprinklers under duct work that exceeds 48 inches. Permit for racking, BLD18-02859 needs to be finaled before life fire safety can be signed off.
Jeff Phone #: ###-####
|
BLD19-04549
| FIRE-Final Inspection | 2/3/2020 | 2/3/2020 | 2/3/2020 11:08:24 AM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher are placed with current inspection tag. Final life fire safety inspection is complete, signature provided on permit sign off card.
Bill- inspection for 11th floor Phone #: ###-####
|
BLD19-04548
| FIRE-Final Inspection | 2/3/2020 | 2/3/2020 | 2/3/2020 11:08:07 AM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher are placed with current inspection tag. Final life fire safety inspection is complete, signature provided on permit sign off card.
Bill- inspection for 1st floor Phone #: ###-####
|
GRD19-00045
| FIRE-Final Inspection | 1/31/2020 | 2/3/2020 | 2/3/2020 11:06:42 AM | P | CANC |
|
|
No signature required for life fire safety as noted in permit details, this request is cancelled.
Phone #: ###-#### Inspection requested via web by Stephen Griswold
|
BLD19-04224
| FIRE-Final Inspection | 1/31/2020 | 2/3/2020 | 2/3/2020 8:01:33 AM | A | FAIL |
|
|
Reference notes entered under FIR19-00932, life fire safety inspection cannot be signed off until FIR permit is finaled, as of this entry as-builts have not been submitted.
John- please call 30 min prior Phone #: ###-####
|
FIR19-00934
| INSP-Final Inspection | 1/31/2020 | 2/3/2020 | 2/3/2020 7:34:05 AM | A | FAIL |
|
|
Speaker strobe in kitchen area is overspaced. A/V device wiring in seating area is attached to fire sprinkler piping, not allowed to attach to sprinkler piping per NFPA13. Three A/V devices in tenant space experience a double flash during active alarm, troubleshoot double flash issue and repair, A/V devices will be required to be activated during next inspection.
Brian Phone #: ###-####
|