Inspections for the day of: Wednesday, February 4, 2004.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00801 INSP-Final Inspection2/3/20042/4/20042/4/2004 12:00:00 AMAFAIL
Sprinkler pendants are overspaced on both sides of the storage room, their square footage runs from 124 to 182 sq. ft.. Sprinkler pendants are overspaced in the copier room. The room is 223 sq. ft. with two pendants in it which is 111 sq. ft. apiece. 1" sch 40 pipe has been used to suspend 1" sch 40 pipe between trusses 32" on center. Per NFPA 13 6.1.1.3a and 6.1.1.3b 1 1/4" pipe should be used. Also the trapeze must be secured to prevent slippage 2/4/2004 11:19:49 AM
BLD03-01135 FIRE-Final Inspection2/3/20042/4/20042/4/2004 12:00:00 AMAPART
Fire life safety given a temporary occupancy until the fire alarm resubmittals have been approved and the alarm system tested. The sprinkler system was given a temp until the fire alarm is tested as well 2/4/2004 9:55:43 AM
FIR03-00448 INSP-Sprinkler Rough-in/Hydro2/3/20042/4/20042/4/2004 12:00:00 AMACANC
Inspection needed was a cover inspection. See fir03-00554 2/4/2004 8:59:18 AM
FIR03-00014 INSP-Final Inspection2/3/20042/4/20042/4/2004 12:00:00 AMAFAIL
Provide strobes in the two basement corridors as discussed 2/4/2004 9:59:40 AM
FIR03-00554 INSP-Sprinkler Rough-in2/4/20042/4/20042/4/2004 12:00:00 AMAPART
Third floor sprinkler piping is ok to cover
FIR03-00419 INSP-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMAPASS
Sprinkler underground finaled
FIR03-00570 INSP-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMAPART
Fire alarm given a temporary occupancy until the fire alarm resubmittals have been approved and the alarm system tested
FIR03-00639 INSP-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMAPART
Fire alarm given a temporary occupancy until the fire alarm resubmittals have been approved and the alarm system tested
FIR03-00769 INSP-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMPFAIL
The contractor replaced the existing battery cabinet with another that is not listed for this use. A minimum of 8 ah batteries are required. 2/4/2004 4:43:48 PM
BLD03-01375 FIRE-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMPPASS
fire life safety finaled
BLD03-01530 FIRE-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMPFAIL
still need handle on the fire extinguisher cabinet in the cafeteria. Fire fly door adjusted and tested
FIR03-00482 INSP-Final Inspection1/30/20042/4/20042/4/2004 12:00:00 AMPPASS
fire alarm finaled 2/4/2004 3:56:50 PM
BLD03-02201 FIRE-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMPCANC
walt; Phone #: ###-#### Internet Inspection Request from: Annette Moore
BLD02-03076 FIRE-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMPPASS
fire life safety finaled 2/4/2004 2:31:51 PM
BLD03-01575 FIRE-Final Inspection2/4/20042/4/20042/4/2004 12:00:00 AMPFAIL
fire alarm plans are not approved yet 2/4/2004 2:03:48 PM