Inspections for the day of: Friday, February 4, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00542 FIR-Aging Inspection2/4/20052/4/20052/4/2005 12:00:00 AM NR
Per Brad Turk work is still in progress and should be done near the end of March. 2/4/2005 2:38:20 PM
BLD04-01734 FIRE-Final Inspection2/4/20052/4/20052/4/2005 12:00:00 AMAFAIL
smoke detector on first floor living area did not set off the other smoke detectors. Need building number and apartment numbers 2/4/2005 10:53:15 AM
FIR04-00477 INSP-Final Inspection2/4/20052/4/20052/4/2005 12:00:00 AMAPASS
Fire alarm finaled
BLD03-03027 FIRE-Final Inspection2/4/20052/4/20052/4/2005 12:00:00 AMAFAIL
Paint curgbing for fire dept access as discussed and marked on approved drawings. Repair the two existing exit signs in the assembly hall. Provide occupant load signs for both assembly areas.
FIR03-00012 INSP-Final Inspection2/3/20052/4/20052/4/2005 12:00:00 AMAPASS
Fire alarm finally finaled! 2/4/2005 11:02:58 AM
FIR04-00057 INSP-Final Inspection2/3/20052/4/20052/4/2005 12:00:00 AMAPASS
corrections made. Hood suppression system operated correctly. 2/4/2005 11:27:10 AM
BLD03-00726 FIRE-Final Inspection2/3/20052/4/20052/4/2005 12:00:00 AMACANC
Already inspected and passed for fire 2/4/2005 9:54:20 AM
FIR04-00546 INSP-Final Inspection2/3/20052/4/20052/4/2005 12:00:00 AMAPASS
Fire sprinkler finaled 2/4/2005 9:56:59 AM
FIR02-00257 INSP-Final Inspection2/4/20052/4/20052/4/2005 12:00:00 AMAPASS
FIR03-00586 INSP-Final Inspection2/4/20052/4/20052/4/2005 12:00:00 AMPFAIL
Provide knox key box. The tamper switches for the backflow preventor did not annunciate separately from the other tamper switch as required by IFC 903.4.1. Need record of completion nfpa form at final. 2/4/2005 3:16:57 PM
FIR04-00754 INSP-Alarm Testing2/4/20052/4/20052/4/2005 12:00:00 AMPFAIL
rand; Phone #: ###-#### I showed up and found there is a trouble on the duct detector zone that the fire alarm contractor is trouble shooting. Inspection to be rescheduled. 2/4/2005 4:05:58 PM