FIR04-00542
| FIR-Aging Inspection | 2/4/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | | NR |
|
|
Per Brad Turk work is still in progress and should be done near the end of March. 2/4/2005 2:38:20 PM
|
BLD04-01734
| FIRE-Final Inspection | 2/4/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | FAIL |
|
|
smoke detector on first floor living area did not set off the other smoke detectors. Need building number and apartment numbers 2/4/2005 10:53:15 AM
|
FIR04-00477
| INSP-Final Inspection | 2/4/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | PASS |
|
|
Fire alarm finaled
|
BLD03-03027
| FIRE-Final Inspection | 2/4/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | FAIL |
|
|
Paint curgbing for fire dept access as discussed and marked on approved drawings. Repair the two existing exit signs in the assembly hall. Provide occupant load signs for both assembly areas.
|
FIR03-00012
| INSP-Final Inspection | 2/3/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | PASS |
|
|
Fire alarm finally finaled! 2/4/2005 11:02:58 AM
|
FIR04-00057
| INSP-Final Inspection | 2/3/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | PASS |
|
|
corrections made. Hood suppression system operated correctly. 2/4/2005 11:27:10 AM
|
BLD03-00726
| FIRE-Final Inspection | 2/3/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | CANC |
|
|
Already inspected and passed for fire 2/4/2005 9:54:20 AM
|
FIR04-00546
| INSP-Final Inspection | 2/3/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler finaled 2/4/2005 9:56:59 AM
|
FIR02-00257
| INSP-Final Inspection | 2/4/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | A | PASS |
|
|
|
FIR03-00586
| INSP-Final Inspection | 2/4/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | P | FAIL |
|
|
Provide knox key box. The tamper switches for the backflow preventor did not annunciate separately from the other tamper switch as required by IFC 903.4.1. Need record of completion nfpa form at final. 2/4/2005 3:16:57 PM
|
FIR04-00754
| INSP-Alarm Testing | 2/4/2005 | 2/4/2005 | 2/4/2005 12:00:00 AM | P | FAIL |
|
|
rand; Phone #: ###-#### I showed up and found there is a trouble on the duct detector zone that the fire alarm contractor is trouble shooting. Inspection to be rescheduled. 2/4/2005 4:05:58 PM
|