ELE08-03160
| Final | 2/4/2009 | 2/4/2009 | 2/4/2009 3:23:57 PM | P | NR |
|
|
UL listings are on back of deadfront, lables have been installed, factory bonding jumper has been installed. Any questions call Emmet ###-#### Phone #: ###-#### Internet Inspection Request from: Emmet Bushman talked with Emmett still needs labels noting ID of different voltages, 210.5 (A&C)
|
ELE05-04231
| Conference | 2/4/2009 | 2/4/2009 | 2/4/2009 2:54:32 PM | P | DONE |
|
|
valeria Phone #: ###-#### Mike this is a straw built house, talked with JIM, wiring will have to meet 2008 NEC if ? call me Jack
|
ELE08-03065
| Final | 2/4/2009 | 2/4/2009 | 2/4/2009 1:39:36 PM | P | FAIL |
|
|
daniel Note: also panel Phone #: ###-#### corr. posted met ele. contr. BCC 4-05-32, and 110.26(F)(1) remove exhaust fan from above main switch gear, BCC4-05-33, and 110.2&3, factory wired cabinets shall be labeled and listed, or ele. contr. can rewire to NEC, note when I told general contr he said that he it was a problem , and Portland inspector posted a correction for the same violation. 210.8 gfci other than dwelling 6ft of sinks and drinking fountain, 250.104, 250.66 bond hot and cold sized to T 250.66, strap MC re-loc 12" of boxes and terminations
|
ELE08-03065
| Permanent Service | 2/4/2009 | 2/4/2009 | 2/4/2009 1:31:14 PM | P | CANC |
|
|
daniel Note: also panel service Phone #: ###-#### no p/s required
|
ELE08-02885
| ELE-Aging Inspection | 2/4/2009 | 2/4/2009 | 2/4/2009 12:11:52 PM | | CANC |
|
|
|
ELE08-02885
| Final | 2/4/2009 | 2/4/2009 | 2/4/2009 12:11:46 PM | P | PASS |
|
|
sign installed, and listed
|
ESC08-01038
| General Inspection | 2/4/2009 | 2/4/2009 | 2/4/2009 11:04:05 AM | A | PASS |
|
|
ok
|
ELE09-00182
| Electrical Rough-In | 2/3/2009 | 2/4/2009 | 2/4/2009 11:03:20 AM | A | PASS |
|
|
Alan Phone #: ###-####needs #6 for other system grd, also call for u/g r/i r/i p/s o/h new ok
|
ELE09-00102
| Rough-In Permanent Service | 2/3/2009 | 2/4/2009 | 2/4/2009 10:31:27 AM | A | FAIL |
|
|
please reinspect, corrections made after talking with Bob. Phone #: ###-#### Internet Inspection Request from: Sean Peltier corr not made still needs nail plates called
|
ELE09-00140
| Final | 2/3/2009 | 2/4/2009 | 2/4/2009 9:39:41 AM | A | PASS |
|
|
Please provide final inspection. Can you please call Travis for access. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok card signed
|
ELE09-00183
| Final | 2/3/2009 | 2/4/2009 | 2/4/2009 8:53:00 AM | A | NR |
|
|
Rod Phone #: ###-#### called
|