Inspections for the day of: Wednesday, February 4, 2009.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00901 INSP-Conference1/28/20091/29/2009 A 
FIR08-00728 FIR-Aging Inspection2/4/20092/4/20092/4/2009 5:07:11 PMPDONE
Site visit confirmed work in progress.
BLD08-01454 FIRE-Conference2/4/20092/4/20092/4/2009 5:06:35 PMPDONE
Discussed fire life safety items needed for final project approval, noted the existing hood suppression system is overdue certification and inspection.
BLD08-01126 FIRE-Final Inspection2/4/20092/4/20092/4/2009 5:04:04 PMPPASS
Okay for final this permit scope.
BLD08-01699 FIRE-Final Inspection2/4/20092/4/20092/4/2009 5:03:12 PMPPASS
Fire life safety site inspection passed.
BLD08-01257 FIRE-Final Inspection2/4/20092/4/20092/4/2009 4:59:39 PMPPART
Portions of the remodel area per red lines on approved plan set sheet E2.0L passed fire life safety inspection. Remainder of permit scope work not yet finished including three rooms and one hallway with new door.
BLD06-01451 FIRE-Conference2/3/20092/4/20092/4/2009 1:30:40 PMADONE
Site visit to verify new light fixtures at residential units do not create obstructions for adjacent sprinkler heads.
FIR08-00766 INSP-Sprinkler Rough-in2/2/20092/4/20092/4/2009 1:27:54 PMAPART
Ductile riser and stub out connection to the yard PIV at the NE corner of the building okayed for cover, discussed bedding material install, noted PIV final adjustment to be provided at 3' above finish grade when complete, see stamped plan set for initials and location of work inspected today.
BLD08-00595 FIRE-Final Inspection2/3/20092/4/20092/4/2009 1:24:12 PMAPASS
Shell building life safety inspection passed, inspection card previously signed.
FIR09-00008 INSP-Sprinkler Rough-in/Hydro2/3/20092/4/20092/4/2009 1:22:43 PMAFAIL
See approved plan set for red-line annotations indicating deficient items including locations where heads are too close to light fixture junction boxes and may become obstructed due to surface mounted lights, ordinary temp. heads must be at least 5' from the front of the fireplace, noted one head too close to a heat diffuser, pendent head at a bedroom is too close to a ceiling fan (maintain min. 3' from the down rod), the CPVC riser must be installed per listing, noted several areas lacking correct tenting for cold cavity protection, missing nailer plates at both main level risers, installation is not approved for cover at this time.