FIR09-00608
| INSP-Final Inspection | 2/4/2010 | 2/4/2010 | 2/4/2010 5:41:21 PM | P | FAIL |
|
|
Smoke detectors at three locations are too close to HVAC diffusers, missing one SD address D1-13, HVAC units must shut down immediately upon duct smoke activation. Fire sprinkler riser supervision tested okay, five MP stations, battery trouble, open circuts, and notification circuts all passed functional testing. Offsite monitoring to be verified under project related FIR permit inspection. Plan resubmittals verified.
|
FIR06-00385
| FIR-Aging Inspection | 2/4/2010 | 2/4/2010 | 2/4/2010 5:34:08 PM | P | NH |
|
|
|
FIR04-00614
| INSP-Final Inspection | 2/4/2010 | 2/4/2010 | 2/4/2010 5:32:09 PM | P | PASS |
|
|
|
BLD09-02135
| FIRE-Conference | 2/4/2010 | 2/4/2010 | 2/4/2010 5:31:32 PM | P | DONE |
|
|
Regarding modifications per the building plans which may affect existing fire sprinkler system coverage.
|
FIR10-00011
| INSP-Sprinkler Rough-in/Hydro | 2/4/2010 | 2/4/2010 | 2/4/2010 5:28:18 PM | A | PART |
|
|
Verified existing head at the elevator hoistway west side per project related plan notes.
|
BLD09-02213
| FIRE-Final Inspection | 2/2/2010 | 2/4/2010 | 2/4/2010 9:37:01 AM | A | PASS |
|
|
Fire life safety is satisfactory, inspection passed.
|
FIR10-00019
| INSP-Final Inspection | 2/3/2010 | 2/4/2010 | 2/4/2010 9:36:21 AM | A | PASS |
|
|
Fire sprinkler final walkthrough passed. TI permit work complete.
|
FIR09-00739
| INSP-Final Inspection | 2/3/2010 | 2/4/2010 | 2/4/2010 9:34:40 AM | A | PASS |
|
|
Fire alarm work passed field testing, permit finaled.
|