Inspections for the day of: Friday, February 4, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-00161 FIRE-Final Inspection2/3/20112/4/20112/4/2011 3:24:46 PMPPASS
Correction items field verified for completion. Fire life safety finaled.
FIR10-00646 INSP-Final Inspection2/3/20112/4/20112/4/2011 3:00:14 PMAPASS
Fire alarm work passed inspection, permit finaled.
FIR10-00300 INSP-Final Inspection2/4/20112/4/20112/4/2011 2:59:17 PMPFAIL
Noted items include; non-functional outside bell, missing escutcheons, secure control valves, signage/calc. info at riser, provide data sheets for exposed supply pipe, pendent head at one room appears obstructed per NFPA 13D 8.2.5.2.1.
BLD11-00115 FIRE-Final Inspection2/4/20112/4/20112/4/2011 12:47:52 PMPPASS
Reinspection passed, noted corrections verified for completion. Life safety finaled.
BLD11-00115 FIRE-Final Inspection2/3/20112/4/20112/4/2011 12:45:57 PMAFAIL
Missing fire extinguisher- certified and posted as discussed.
FIR10-00463 INSP-Final Inspection2/3/20112/4/20112/4/2011 11:56:27 AMAPASS
Fire sprinkler permit work passed final inspection.
FIR10-00653 INSP-Final Inspection2/2/20112/4/20112/2/2011 3:43:50 PMACANC
Mike B is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR10-00355 INSP-Final Inspection2/2/20112/4/20112/2/2011 3:43:36 PMACANC
Mike B is the contact. We understand this is scheduled for 7:30 am. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus