Inspections for the day of: Wednesday, February 4, 2015.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-03166 Final2/4/20152/4/20152/4/2015 3:25:40 PMPFAIL
Phone #: ###-#### Inspection requested via web by Celinda Winters
314.25- All boxes shall have covers. 2 open boxes in copy area. Secure cover on out service.
358.30- Secure EMT conduits with in 3' above service enclosure.
ELE14-02676 Electrical Rough-In2/3/20152/4/20152/4/2015 2:40:55 PMPPASS
Wall Cover. Toby is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen This is building 2. Wall and hardlid rough in ok cover
ELE14-02676 Permanent Service2/3/20152/4/20152/4/2015 2:40:01 PMPPASS
Toby is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen p/s u/g n ok
ELE14-02796 Final2/4/20152/4/20152/4/2015 1:48:46 PMPNR
Looking to get temporary final this late afternoon and rest of final on friday. If we could time the inspection towards the end of the day today would be appreciate it. Phone #: ###-#### Inspection requested via web by Thomas Jenkins 314.25 All boxes shall have covers. Multiple covers missing that are accessible to public. Street light cover missing on parking lot light N.E. corner of store. All floor boxes. 6 gang in hall. Will rescedule
ELE15-00283 Electrical Rough-In2/4/20152/4/20152/4/2015 1:24:29 PMPPASS
ceiling inspection. please call before heading that way. Chris is contact. Thanks! Phone #: ###-#### Inspection requested via web by Chris Chesnut 210.62- This space does not have a specific occupant. Show winsow receptacle outlets shall be installed for final. Grid rough in ok cover
ELE15-00216 Final2/3/20152/4/20152/4/2015 1:02:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Fletcher Deck and tub removed work space ok. Final ok
ELE15-00171 Electrical Rough-In2/3/20152/4/20152/4/2015 12:45:26 PMPPASS
Inspect ceiling for sheetrock cover in front entry. Phone #: ###-#### Inspection requested via web by robert feller Foyer hardlid and patch foyer walls rough in ok cover
ELE15-00295 Final2/4/20152/4/20152/4/2015 12:29:01 PMPPASS
Phone #: ###-#### Inspection requested via web by ron spen cer t/s u/g n ok
ELE15-00272 Final2/3/20152/4/20152/4/2015 11:37:27 AMAFAIL
front door code 23579 or garage door code 3655
Thanks!! Phone #: ###-#### Inspection requested via web by Richard Gratiot
110.7- Wiring shall be complete. Open ground in dining room. Open neutral in basement bed.
210.8- All garage receptacle outlets located in garage shall have GFCI protection.
300.15- Dishwasher wire shall terminate in a box.
314.16- Box located in basement storage room overfilled. Has 7 12-2 MN cables terminated in it.
314.20- Receptacle outlets located in basement on wood panelling shall be flush or have spark rings installed.
334.30- MN cable located in basement storage room shall be secured within `12" of boxes and every 4 1/2'.
408.4- Complete panel directory.
ELE14-02029 open on property for service reconnect. Most recent contractor said he would complete panel derectory
ELE14-01947 Final2/3/20152/4/20152/4/2015 10:15:58 AMAPASS
3 Sets Pan Channel Lettering - final Phone #: ###-#### Inspection requested via web by Dana Vance UL listing and disconnecting means confirmed. Final ok
ELE14-02543 Final2/3/20152/4/20152/4/2015 10:07:35 AMANH
Please contact the homeowners Tom or Jeanie Whitney for access. Thanks Phone #: ###-#### Inspection requested via web by steve ragan
No answer left message will reschedule when someone is available
ELE15-00282 Temporary Service2/3/20152/4/20152/4/2015 9:26:11 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE15-00278 Temporary Service2/3/20152/4/20152/4/2015 9:16:08 AMACANC
Phone #: ###-#### Inspection requested via web by Darryn Coburn Temp pole all ready exists on address on ele14-01426
ELE15-00281 Temporary Service2/3/20152/4/20152/4/2015 9:15:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE15-00280 Temporary Service2/3/20152/4/20152/4/2015 9:01:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE15-00279 Temporary Service2/3/20152/4/20152/4/2015 8:49:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
ELE15-00284 Temporary Service2/3/20152/4/20152/4/2015 8:08:44 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
ELE10-01304 ELE-Aging Inspection2/4/20152/4/20152/4/2015 6:43:54 AM CANC
too busy
ELE12-00179 ELE-Aging Inspection2/4/20152/4/20152/4/2015 6:43:41 AM CANC
too busy