ELE14-03166
| Final | 2/4/2015 | 2/4/2015 | 2/4/2015 3:25:40 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters 314.25- All boxes shall have covers. 2 open boxes in copy area. Secure cover on out service. 358.30- Secure EMT conduits with in 3' above service enclosure.
|
ELE14-02676
| Electrical Rough-In | 2/3/2015 | 2/4/2015 | 2/4/2015 2:40:55 PM | P | PASS |
|
|
Wall Cover. Toby is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen This is building 2. Wall and hardlid rough in ok cover
|
ELE14-02676
| Permanent Service | 2/3/2015 | 2/4/2015 | 2/4/2015 2:40:01 PM | P | PASS |
|
|
Toby is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen p/s u/g n ok
|
ELE14-02796
| Final | 2/4/2015 | 2/4/2015 | 2/4/2015 1:48:46 PM | P | NR |
|
|
Looking to get temporary final this late afternoon and rest of final on friday. If we could time the inspection towards the end of the day today would be appreciate it. Phone #: ###-#### Inspection requested via web by Thomas Jenkins 314.25 All boxes shall have covers. Multiple covers missing that are accessible to public. Street light cover missing on parking lot light N.E. corner of store. All floor boxes. 6 gang in hall. Will rescedule
|
ELE15-00283
| Electrical Rough-In | 2/4/2015 | 2/4/2015 | 2/4/2015 1:24:29 PM | P | PASS |
|
|
ceiling inspection. please call before heading that way. Chris is contact. Thanks! Phone #: ###-#### Inspection requested via web by Chris Chesnut 210.62- This space does not have a specific occupant. Show winsow receptacle outlets shall be installed for final. Grid rough in ok cover
|
ELE15-00216
| Final | 2/3/2015 | 2/4/2015 | 2/4/2015 1:02:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Randy Fletcher Deck and tub removed work space ok. Final ok
|
ELE15-00171
| Electrical Rough-In | 2/3/2015 | 2/4/2015 | 2/4/2015 12:45:26 PM | P | PASS |
|
|
Inspect ceiling for sheetrock cover in front entry. Phone #: ###-#### Inspection requested via web by robert feller Foyer hardlid and patch foyer walls rough in ok cover
|
ELE15-00295
| Final | 2/4/2015 | 2/4/2015 | 2/4/2015 12:29:01 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by ron spen cer t/s u/g n ok
|
ELE15-00272
| Final | 2/3/2015 | 2/4/2015 | 2/4/2015 11:37:27 AM | A | FAIL |
|
|
front door code 23579 or garage door code 3655 Thanks!! Phone #: ###-#### Inspection requested via web by Richard Gratiot 110.7- Wiring shall be complete. Open ground in dining room. Open neutral in basement bed. 210.8- All garage receptacle outlets located in garage shall have GFCI protection. 300.15- Dishwasher wire shall terminate in a box. 314.16- Box located in basement storage room overfilled. Has 7 12-2 MN cables terminated in it. 314.20- Receptacle outlets located in basement on wood panelling shall be flush or have spark rings installed. 334.30- MN cable located in basement storage room shall be secured within `12" of boxes and every 4 1/2'. 408.4- Complete panel directory. ELE14-02029 open on property for service reconnect. Most recent contractor said he would complete panel derectory
|
ELE14-01947
| Final | 2/3/2015 | 2/4/2015 | 2/4/2015 10:15:58 AM | A | PASS |
|
|
3 Sets Pan Channel Lettering - final Phone #: ###-#### Inspection requested via web by Dana Vance UL listing and disconnecting means confirmed. Final ok
|
ELE14-02543
| Final | 2/3/2015 | 2/4/2015 | 2/4/2015 10:07:35 AM | A | NH |
|
|
Please contact the homeowners Tom or Jeanie Whitney for access. Thanks Phone #: ###-#### Inspection requested via web by steve ragan No answer left message will reschedule when someone is available
|
ELE15-00282
| Temporary Service | 2/3/2015 | 2/4/2015 | 2/4/2015 9:26:11 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-00278
| Temporary Service | 2/3/2015 | 2/4/2015 | 2/4/2015 9:16:08 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Temp pole all ready exists on address on ele14-01426
|
ELE15-00281
| Temporary Service | 2/3/2015 | 2/4/2015 | 2/4/2015 9:15:10 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-00280
| Temporary Service | 2/3/2015 | 2/4/2015 | 2/4/2015 9:01:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-00279
| Temporary Service | 2/3/2015 | 2/4/2015 | 2/4/2015 8:49:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE15-00284
| Temporary Service | 2/3/2015 | 2/4/2015 | 2/4/2015 8:08:44 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
|
ELE10-01304
| ELE-Aging Inspection | 2/4/2015 | 2/4/2015 | 2/4/2015 6:43:54 AM | | CANC |
|
|
too busy
|
ELE12-00179
| ELE-Aging Inspection | 2/4/2015 | 2/4/2015 | 2/4/2015 6:43:41 AM | | CANC |
|
|
too busy
|