Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02008 ELE-Aging Inspection2/4/20162/4/20162/4/2016 4:10:34 PM PASS
Due to new state law listing not required for industrial machines. ok final
ELE13-02008 Final2/4/20162/4/20162/4/2016 4:09:59 PMPPASS
Listing no longer law, Final ok
ELE12-02132 ELE-Aging Inspection2/4/20162/4/20162/4/2016 4:04:33 PM PASS
Waiting on contractor
ELE12-01934 ELE-Aging Inspection2/4/20162/4/20162/4/2016 4:02:13 PM PASS
Waiting for access
ELE16-00335 Final2/4/20162/4/20162/4/2016 3:58:55 PMPPASS
Ben Phone #: ###-#### No access to area due to secure area at airport ticket area behind counter and was denied access. Contractor sent photos. Just 1 receptacle added for monitor. Final ok
ELE16-00335 Electrical Rough-In2/4/20162/4/20162/4/2016 3:03:40 PMPPASS
Ben Phone #: ###-#### All surface mount conduit. Rough in ok
ELE16-00091 Permanent Service2/3/20162/4/20162/4/2016 2:55:40 PMPPASS
Contact is Matt Brown Phone #: ###-#### Inspection requested via web by Scott Campbell 65K rated main with 31K available fault current. p/s u/g n ok
ELE15-03661 Electrical Rough-In2/4/20162/4/20162/4/2016 2:35:26 PMPPASS
please contact prior to inspection. ###-#### Ceiling and wall cover Phone #: ###-#### Inspection requested via web by BARRY KENDALL
Part of demizing wall noted on contractor print and grid on federal side only rough in ok cover
GCE15-00150 GCE-Final2/3/20162/4/20162/4/2016 1:44:16 PMPFAIL
Darrin ###-####
210.8- All receptcals serving kitchen counter top area shall have GFCI protection.
Receptacle has not been installed for microwave. Both in studio
GCE15-00155 GCE-Final2/3/20162/4/20162/4/2016 1:11:06 PMPFAIL
Darrin ###-####
300.15- Furnace splice or termination shall be in a box.
314.20- Where box is installed in a combustible material it shall be flush or extension ring shall be installed to make flush. Boxes in wood trim.
334.12(B)- NM Caable where ran exposed shall be protected from physical damage. Furnace.
440.14- A disconnecting means shall be provided for furnace.
ELE16-00350 Temporary Service2/4/20162/4/20162/4/2016 12:33:14 PMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
GCE15-00148 GCE-Rough-In Permanent Service2/3/20162/4/20162/4/2016 11:26:18 AMAPASS
Eric ###-#### Check panel for single neutral per termination and receptacle for fixed panel in dining room. Rough in ok cover p/s u/g n ok
ELE16-00305 Rough-In Permanent Service2/1/20162/4/20162/4/2016 10:39:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE15-03895 Final2/4/20162/4/20162/4/2016 9:59:20 AMAPASS
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE15-03923 Final2/4/20162/4/20162/4/2016 9:29:07 AMAPASS
Garage code 2020E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok