ELE13-02008
| ELE-Aging Inspection | 2/4/2016 | 2/4/2016 | 2/4/2016 4:10:34 PM | | PASS |
|
|
Due to new state law listing not required for industrial machines. ok final
|
ELE13-02008
| Final | 2/4/2016 | 2/4/2016 | 2/4/2016 4:09:59 PM | P | PASS |
|
|
Listing no longer law, Final ok
|
ELE12-02132
| ELE-Aging Inspection | 2/4/2016 | 2/4/2016 | 2/4/2016 4:04:33 PM | | PASS |
|
|
Waiting on contractor
|
ELE12-01934
| ELE-Aging Inspection | 2/4/2016 | 2/4/2016 | 2/4/2016 4:02:13 PM | | PASS |
|
|
Waiting for access
|
ELE16-00335
| Final | 2/4/2016 | 2/4/2016 | 2/4/2016 3:58:55 PM | P | PASS |
|
|
Ben Phone #: ###-#### No access to area due to secure area at airport ticket area behind counter and was denied access. Contractor sent photos. Just 1 receptacle added for monitor. Final ok
|
ELE16-00335
| Electrical Rough-In | 2/4/2016 | 2/4/2016 | 2/4/2016 3:03:40 PM | P | PASS |
|
|
Ben Phone #: ###-#### All surface mount conduit. Rough in ok
|
ELE16-00091
| Permanent Service | 2/3/2016 | 2/4/2016 | 2/4/2016 2:55:40 PM | P | PASS |
|
|
Contact is Matt Brown Phone #: ###-#### Inspection requested via web by Scott Campbell 65K rated main with 31K available fault current. p/s u/g n ok
|
ELE15-03661
| Electrical Rough-In | 2/4/2016 | 2/4/2016 | 2/4/2016 2:35:26 PM | P | PASS |
|
|
please contact prior to inspection. ###-#### Ceiling and wall cover Phone #: ###-#### Inspection requested via web by BARRY KENDALL Part of demizing wall noted on contractor print and grid on federal side only rough in ok cover
|
GCE15-00150
| GCE-Final | 2/3/2016 | 2/4/2016 | 2/4/2016 1:44:16 PM | P | FAIL |
|
|
Darrin ###-#### 210.8- All receptcals serving kitchen counter top area shall have GFCI protection. Receptacle has not been installed for microwave. Both in studio
|
GCE15-00155
| GCE-Final | 2/3/2016 | 2/4/2016 | 2/4/2016 1:11:06 PM | P | FAIL |
|
|
Darrin ###-#### 300.15- Furnace splice or termination shall be in a box. 314.20- Where box is installed in a combustible material it shall be flush or extension ring shall be installed to make flush. Boxes in wood trim. 334.12(B)- NM Caable where ran exposed shall be protected from physical damage. Furnace. 440.14- A disconnecting means shall be provided for furnace.
|
ELE16-00350
| Temporary Service | 2/4/2016 | 2/4/2016 | 2/4/2016 12:33:14 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
|
GCE15-00148
| GCE-Rough-In Permanent Service | 2/3/2016 | 2/4/2016 | 2/4/2016 11:26:18 AM | A | PASS |
|
|
Eric ###-#### Check panel for single neutral per termination and receptacle for fixed panel in dining room. Rough in ok cover p/s u/g n ok
|
ELE16-00305
| Rough-In Permanent Service | 2/1/2016 | 2/4/2016 | 2/4/2016 10:39:56 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE15-03895
| Final | 2/4/2016 | 2/4/2016 | 2/4/2016 9:59:20 AM | A | PASS |
|
|
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE15-03923
| Final | 2/4/2016 | 2/4/2016 | 2/4/2016 9:29:07 AM | A | PASS |
|
|
Garage code 2020E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|