ELE19-00116
| Electrical Rough-In | 2/4/2019 | 2/4/2019 | 2/4/2019 2:30:26 PM | P | PASS |
|
|
Roughed in Conduit for future solar project. Conduit is labeled and runs from roof down to pull box near electrical panel. Phone #: ###-#### Inspection requested via web by Jesse Simpson Solar conduit only from roof to boxes next to panel in garage rough in ok cover
|
ELE19-00418
| Electrical Rough-In | 2/4/2019 | 2/4/2019 | 2/4/2019 1:51:41 PM | P | PASS |
|
|
Please give me half an hour notice before inspection to insure access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Single basin in master bath, 2 hot and cold faucets with single drain, areas noted rough in ok cover
|
ELE19-00414
| Temporary Service | 2/3/2019 | 2/4/2019 | 2/4/2019 1:18:56 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Schaffer 230.62- Live parts shall be guarded from accidental contact. 3 out of 4 cover screws missing. 250.24- Grounded conductor shall be connected to a grounding electrode conductor. Unable to locate main bonding jumper.
|
ELE17-02862
| Final | 2/4/2019 | 2/4/2019 | 2/4/2019 10:21:44 AM | A | PASS |
|
|
TCO on 5TH floor deck and sign off on final Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Oirginal permit not provided, signed all TCO sheets for final. Final ok
|
ELE18-04785
| Electrical Rough-In | 2/3/2019 | 2/4/2019 | 2/4/2019 9:25:32 AM | A | PASS |
|
|
Uffer Phone #: ###-#### Inspection requested via web by Tom Jenkins Concrete encased electrode for maintainance building rough in ok cover
|
ELE19-00410
| Temporary Service | 2/1/2019 | 2/4/2019 | 2/4/2019 9:04:35 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 590.6(B)- Temporary power receptacles other than 120 volt shall have GFCI protection. Standard 50 amp breaker installed.
|
ELE19-00413
| Electrical Rough-In | 2/3/2019 | 2/4/2019 | 2/4/2019 8:52:44 AM | A | PASS |
|
|
Good morning, I am requesting a rough in inspection of this addition. There is access to the back by either the alley which the fence is down or by the front by going through the open carport. Thank you Phone #: ###-#### Inspection requested via web by todd cline Master bed, bath, and utility addition rough in ok cover
|