Inspections for the day of: Monday, February 4, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00116 Electrical Rough-In2/4/20192/4/20192/4/2019 2:30:26 PMPPASS
Roughed in Conduit for future solar project. Conduit is labeled and runs from roof down to pull box near electrical panel. Phone #: ###-#### Inspection requested via web by Jesse Simpson
Solar conduit only from roof to boxes next to panel in garage rough in ok cover
ELE19-00418 Electrical Rough-In2/4/20192/4/20192/4/2019 1:51:41 PMPPASS
Please give me half an hour notice before inspection to insure access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Single basin in master bath, 2 hot and cold faucets with single drain, areas noted rough in ok cover
ELE19-00414 Temporary Service2/3/20192/4/20192/4/2019 1:18:56 PMAFAIL
Phone #: ###-#### Inspection requested via web by Ryan Schaffer
230.62- Live parts shall be guarded from accidental contact. 3 out of 4 cover screws missing.
250.24- Grounded conductor shall be connected to a grounding electrode conductor. Unable to locate main bonding jumper.
ELE17-02862 Final2/4/20192/4/20192/4/2019 10:21:44 AMAPASS
TCO on 5TH floor deck and sign off on final Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Oirginal permit not provided, signed all TCO sheets for final. Final ok
ELE18-04785 Electrical Rough-In2/3/20192/4/20192/4/2019 9:25:32 AMAPASS
Uffer Phone #: ###-#### Inspection requested via web by Tom Jenkins
Concrete encased electrode for maintainance building rough in ok cover
ELE19-00410 Temporary Service2/1/20192/4/20192/4/2019 9:04:35 AMAFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI
590.6(B)- Temporary power receptacles other than 120 volt shall have GFCI protection. Standard 50 amp breaker installed.
ELE19-00413 Electrical Rough-In2/3/20192/4/20192/4/2019 8:52:44 AMAPASS
Good morning, I am requesting a rough in inspection of this addition. There is access to the back by either the alley which the fence is down or by the front by going through the open carport. Thank you Phone #: ###-#### Inspection requested via web by todd cline
Master bed, bath, and utility addition rough in ok cover