FIR19-00797
| INSP-Sprinkler Rough-in | 2/4/2020 | 2/4/2020 | 2/4/2020 3:04:33 PM | P | PASS |
|
|
Rough to cover inspection for scope of work is complete, scope of work is approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-04224
| FIRE-Final Inspection | 2/4/2020 | 2/4/2020 | 2/4/2020 2:37:01 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for scope of work is complete, signatures provided on permit sign off card.
|
FIR19-00932
| INSP-Final Inspection | 2/4/2020 | 2/4/2020 | 2/4/2020 2:35:46 PM | P | PASS |
|
|
As-builts have been accepted, final fire alarm inspection for scope of work complete.
|
BLD18-01391
| FIRE-Final Inspection | 2/3/2020 | 2/4/2020 | 2/4/2020 12:30:47 PM | A | FAIL |
|
|
Called point of contact listed at 0945, left message with my contact information and stated that if a return call was not made by 1000 then I was going to proceed to next inspection. Inspection request was left open until 12:30PM with no return call, inspection request will need to be rescheduled.
Life Safety Final Phone #: ###-#### Inspection requested via web by Wayne Berry
|
BLD19-02947
| FIRE-Final Inspection | 2/3/2020 | 2/4/2020 | 2/4/2020 12:30:31 PM | A | FAIL |
|
|
Called point of contact listed at 0945, left message with my contact information and stated that if a return call was not made by 1000 then I was going to proceed to next inspection. Inspection request was left open until 12:30PM with no return call, inspection request will need to be rescheduled.
life Safety Inspection Phone #: ###-#### Inspection requested via web by Wayne Berry
|
FIR20-00018
| INSP-Sprinkler Rough-in | 2/3/2020 | 2/4/2020 | 2/4/2020 9:42:17 AM | A | PART |
|
|
Rough to cover inspection for All Valley scope of work is complete, scope of work is approved for cover at contractors discertion. Will need to verify calculations to support more than 1 head off of 1 inch piping, numerous areas throughout the existing section of tenant space have more than 1 head off of 1 inch pipe and approved plans show only 1 head off of 1 inch piping, corrections may be required. Need to verify compatibility between concelaed fusible link heads and the 155 quick response glass bulb heads, concealer heads are shown as 155 quick response heads on city approved drawings. A seperate rough in inspection will be required before final inspection to verify more than 1 head off of 1 inch piping as well as concealed/recessed head compatability.
peyton Phone #: ###-####
|
BLD19-04158
| FIRE-Final Inspection | 2/3/2020 | 2/4/2020 | 2/4/2020 8:44:30 AM | A | PASS |
|
|
Final life fire safety inspection for area of work is complete.
please call 20 before thanks Phone #: ###-#### Inspection requested via web by Todd Landvatter
|
FIR20-00041
| INSP-Final Inspection | 1/28/2020 | 2/4/2020 | 2/4/2020 8:19:32 AM | A | CANC |
|
|
Inspection scheduled for the wrong date, this request is cancelled per conversation with point of contact.
Needs to be @ 7 am as the building is occupied. Phone #: ###-#### Inspection requested via web by Kristin Dolan
|