Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-00274 Electrical Rough-In2/4/20022/5/20022/5/2002 12:00:00 AMAFAIL
###-#### cor. posted corrections not made still needs to set outside boxes flush with ceder siding( combustible material) called left message 2/5/2002 12:03:49 PM
ELE01-04301 Final2/4/20022/5/20022/5/2002 12:00:00 AMAPASS
###-#### ok 2/5/2002 12:30:51 PM
ELE01-04212 Electrical Rough-In2/4/20022/5/20022/5/2002 12:00:00 AMAPART
r/i- george ###-#### walls and ceiling 2/5/2002 10:31:53 AM
ELE02-00263 Electrical Rough-In2/4/20022/5/20022/5/2002 12:00:00 AMAFAIL
ROCO - ###-#### cor. posted meet with homeowner see JF for details C O W 2/5/2002 11:46:43 AM
ELE01-02029 Final2/4/20022/5/20022/5/2002 12:00:00 AMANH
Scheduled by a contractor via Hello! on 02/04/2002 at 20:35:53. Contact: ###-####. notice posted 2/5/2002 9:53:00 AM
ELE01-03915 Electrical Rough-In2/5/20022/5/20022/5/2002 12:00:00 AMPFAIL
###-#### CARL cor. posted meet with homeowner see JF for details C O W 2/5/2002 4:20:00 PM
ELE02-00261 Final2/5/20022/5/20022/5/2002 12:00:00 AMPFAIL
###-#### 2/5/2002 6:29:54 PM see jf for details 2/5/2002 6:30:04 PM
ELE02-00296 Final2/5/20022/5/20022/5/2002 12:00:00 AMPFAIL
###-#### cor. posted called 110.3(b)shall not type off of factory wire bus in p/s shall install manufactures listed fuse block in blank space for a/c branch circuit, 240.52 shall install type S fuses where evidence of overfusing, 210.63 shall provide gfci protected outside outlet for a/c 2/5/2002 5:45:39 PM