MEC03-03502
| Final | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Bruce Younger
Need 6" clearance to single wall vent basement and second level. Overflow installed to ac second level and terminate to visible location. 2/5/2004 9:59:20 AM
|
MEC04-00264
| Final | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | A | PASS |
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
MEC04-00310
| Rough-in | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/4/2004 at 2:26:20 PM. Contact: ###-####.
|
MEC04-00310
| Pressure Test | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 2/4/2004 at 2:26:39 PM. Contact: ###-####.
|
MEC04-00329
| Pressure Test | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | A | FAIL |
|
|
PLEASE CALL DENTON NEED ROUGH IN AND PRESSURE TEST. THANKS!; Phone #: ###-#### Internet Inspection Request from: RaChelle Meister
Need termination fitting at exterior to support meter. CSST under house connection to hard pipe is kinked, see installation instructions for minimum radius bends allowed. 2/5/2004 12:18:04 PM
|
MEC03-03483
| Final | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | A | PASS |
|
|
todd ###-####
|
BLD03-02207
| BLD-Wall cover | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | P | FAIL |
|
|
int.shear inspection; Phone #: ###-#### Internet Inspection Request from: Erby Gonzales
Plans call for each side to sheared. Contractor to get letter from designer verifing that one side is to be sheared only. 2/5/2004 1:58:25 PM
|
BLD03-02201
| BLD-Final | 2/5/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | P | CANC |
|
|
walt--late pm if possible; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
MEC04-00329
| Rough-in | 2/5/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | P | FAIL |
|
|
Need sheet metal sleeve at B-Vent in attic.
|
BLD03-03056
| BLD-Framing/Rough-in | 2/4/2004 | 2/5/2004 | 2/5/2004 12:00:00 AM | P | PASS |
|
|
mark; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
ok to insulate only 2/5/2004 2:44:23 PM
|