ELE07-00390
| Permanent Service | 2/3/2007 | 2/5/2007 | 2/5/2007 3:17:35 PM | P | PASS |
|
|
Phone #: ###-#### corr. called for r/i 300.4 nail plates and 11/4", 110.3(B) & 314.4 needs bond bushing for steel flex where it enters plastic enclosure p/s u/g new ok
|
ELE07-00379
| Permanent Service | 2/5/2007 | 2/5/2007 | 2/5/2007 2:35:19 PM | P | PASS |
|
|
Joe - per Jack set for 1:00; Phone #: ###-#### Internet Inspection Request from: Darla Downs p/s u/g rec ok
|
ELE07-00397
| Final | 2/5/2007 | 2/5/2007 | 2/5/2007 1:45:59 PM | P | NR |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|
ELE07-00397
| Electrical Rough-In | 2/5/2007 | 2/5/2007 | 2/5/2007 1:45:28 PM | P | FAIL |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr. called 210.52(A) shall prvide reqired outlets for spacing, 314.16 correct all box fill, 300.10&12 shall maintain elect. and mech. continunity of raceways flex from box to wall heater and wiremold, 386.2, 21, 100 shall use listed fittings for wiremold, shall not run romex in wiremold, provide abrasion protection
|
ELE07-00395
| Permanent Service | 2/5/2007 | 2/5/2007 | 2/5/2007 12:43:22 PM | P | FAIL |
|
|
Unit #6. Work performed by Ron Chaney. Phone #: ###-#### corr. called550.10(AthurH) cord shall meet requirements, cord is buried, and damaged, 550.11(D) shall provide 50 amps not 60, BCC shall make corrections or power could be diconnected
|
ELE06-03996
| Final | 2/5/2007 | 2/5/2007 | 2/5/2007 12:05:46 PM | P | PASS |
|
|
please call for access code, rock-###-#### Phone #: ###-#### ok both units
|
ELE07-00379
| Final | 2/2/2007 | 2/5/2007 | 2/5/2007 10:03:40 AM | A | CANC |
|
|
Call Jim Allen for appt. to get in house. ###-#### cell, ###-#### home. Phone #: ###-#### called contr canceled
|
ELE07-00343
| Rough-In Permanent Service | 2/5/2007 | 2/5/2007 | 2/5/2007 10:02:53 AM | A | PASS |
|
|
Phone #: ###-#### r/i p/s u/g for meter ok
|
ELE07-00393
| Electrical Rough-In | 2/5/2007 | 2/5/2007 | 2/5/2007 9:17:34 AM | P | PASS |
|
|
zane ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall r/i garage ok
|
ELE07-00393
| Permanent Service | 2/5/2007 | 2/5/2007 | 2/5/2007 9:17:06 AM | A | PASS |
|
|
zane ; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s u/g new ok for garage only
|
ELE07-00308
| Rough-In Permanent Service | 2/2/2007 | 2/5/2007 | 2/5/2007 9:14:18 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 2/2/2007 at 12:38:33 PM. Contact: ###-####. corr. called 300.4 nail plates, 210.52(A) outlets required stair wall kit. din., liv. rm wall by entry, 250.122 needs #12 equip grd wire kit, where 12&14 are in same box, corr for low voltage. bld06-02488 300.4(A)(1)&(D) nail plates and 11/4" for cables parallel to framing members
|
ELE07-00368
| Temporary Service | 2/2/2007 | 2/5/2007 | 2/5/2007 8:07:04 AM | A | PASS |
|
|
CHAD; Phone #: ###-#### Internet Inspection Request from: Victoria Beall t/s u/g new ok
|