BLD07-02976
| FIRE-Final Inspection | 2/5/2008 | 2/5/2008 | 2/5/2008 4:26:29 PM | P | NR |
|
|
Fire life safety to be completed after fire alarm and sprinkler permit finals.
|
BLD07-02977
| FIRE-Final Inspection | 2/5/2008 | 2/5/2008 | 2/5/2008 4:25:19 PM | P | NR |
|
|
Pending fire alarm work.
|
BLD07-02975
| FIRE-Final Inspection | 2/5/2008 | 2/5/2008 | 2/5/2008 4:24:42 PM | P | NR |
|
|
Need project related fire alarm and sprinkler permit finals.
|
FIR08-00002
| INSP-Final Inspection | 2/4/2008 | 2/5/2008 | 2/5/2008 3:40:19 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00767
| INSP-Final Inspection | 2/4/2008 | 2/5/2008 | 2/5/2008 3:39:41 PM | A | FAIL |
|
|
Missing two heads at the underfloor area relocated branchline, one underfloor head adjacent to the new stocker is not supplied by 1 1/4 per plan, need to relocate one OH sprinkler outside the new tool-locate per approved drawings.
|
FIR07-00883
| INSP-Final Inspection | 2/4/2008 | 2/5/2008 | 2/5/2008 12:33:56 PM | A | PASS |
|
|
Remainder of fire alarm testing passed per scope of alarm work for phase 2, also tested one av and two SD as clouded and initialed on this set of approved plans for an adjacent permit area.
|
FIR07-00846
| INSP-Final Inspection | 2/4/2008 | 2/5/2008 | 2/5/2008 11:57:19 AM | A | PASS |
|
|
One overspaced notification device adjusted for correct cd while on site, fire alarm testing passed, permit finaled.
|
BLD07-03090
| FIRE-Conference | 2/4/2008 | 2/5/2008 | 2/5/2008 11:48:49 AM | A | DONE |
|
|
Site conference regarding hardware issues for relocated doors, also discussed project related fire alarm and sprinkler permits required.
|
BLD07-03089
| FIRE-Conference | 2/4/2008 | 2/5/2008 | 2/5/2008 11:46:30 AM | A | DONE |
|
|
On site visit to discuss door hardware requirements at the new terrace seating area per fire code review notes.
|
FIR08-00037
| INSP-Sprinkler Rough-in | 2/4/2008 | 2/5/2008 | 2/5/2008 11:20:21 AM | P | CANC |
|
|
OH Cover Inspection
Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|