Inspections for the day of: Tuesday, February 5, 2008.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03752 Permanent Service2/4/20082/5/20082/5/2008 5:00:36 PMPFAIL
rod Phone #: ###-#### nec408.36(F) brker lock down in main panel. nec408.7 unused openings in sub panel old sub panel. note oked service swing over roof (nec230.230.24A)
ELE08-00268 Rough-In Permanent Service2/5/20082/5/20082/5/2008 4:24:42 PMPNR
please final this also, as we are finished with this project. the spa equipment is not ours. Phone #: ###-#### Internet Inspection Request from: Sean Peltier called had conf with sean under ground conduit needs to be rigid or imc (under concrete for pvc) two ground rods, lock down main breaker in garage panel, & meet for conf. or clean up old unsafe wiring.
ELE08-00272 Temporary Service2/5/20082/5/20082/5/2008 12:26:31 PMPPASS
ron Phone #: ###-#### t/s u/g n ok
ELE07-04222 Final2/4/20082/5/20082/5/2008 11:46:33 AMAPASS
rick Phone #: ###-#### ok final
ELE08-00262 Rough-In Permanent Service2/4/20082/5/20082/5/2008 9:45:10 AMANH
CONTACT JACK ELECTRICAL R/I & SERVICE Phone #: ###-#### Internet Inspection Request from: Emmet Bushman no access called jack & advised reinspection fee
ELE06-04709 Final2/4/20082/5/20082/5/2008 9:09:19 AMAPASS
Plaese inspect outlet for weather station by south east corner of roof , see the custodian for access Phone #: ###-#### Internet Inspection Request from: gary batten ok final