Inspections for the day of: Tuesday, February 5, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00365 INSP-Final Inspection2/4/20082/5/20082/5/2008 4:32:41 PMAPASS
Permit finaled
BLD06-02599 FIRE-Final Inspection2/5/20082/5/20082/5/2008 4:28:16 PMPFAIL
Repair the emergency lights as marked on the city approved plans. Provide current inspections for the fire extinguishers in the breakroom and the computer room.
FIR08-00009 INSP-Final Inspection2/4/20082/5/20082/5/2008 4:00:00 PMPFAIL
The sprinkler heads are overspaced. Per Jake this will be remedied and called for re-inspection tomorrow.
FIR07-00546 INSP-Sprinkler Rough-in2/5/20082/5/20082/5/2008 3:58:40 PMPPASS
As-builts need to be provided showing the additional heads. Several heads need tape and foil removed. Provide aux. drain on west end of system as per plans. Provide the correct backflow or provide resubmittals for friction loss verification. Still need to hydro, forward flush and the other finishing touches.
FIR07-00578 INSP-Sprinkler Rough-in1/31/20082/5/20082/5/2008 1:52:24 PMAPASS
See the city approved plans for piping locations approved for cover.
BLD07-02990 FIRE-Final Inspection2/4/20082/5/20082/5/2008 12:14:52 PMAPASS
fire life safety passed
BLD07-01555 FIRE-Final Inspection2/4/20082/5/20082/5/2008 11:38:24 AMAPART
A temporary occupancy was given with sam rogers permission until the correct door hardware is provided on the northwest exit doors.