Inspections for the day of: Thursday, February 5, 2009.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00041 Final2/5/20092/5/20092/5/2009 4:35:11 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Bryan Atkins ok
ELE09-00042 Final2/5/20092/5/20092/5/2009 4:34:52 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Bryan Atkins ok
ELE09-00040 Final2/5/20092/5/20092/5/2009 4:34:37 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Bryan Atkins ok
ELE09-00053 Final2/5/20092/5/20092/5/2009 3:46:41 PMPPASS
###-#### Internet Inspection Request from: Todd Holbrook ok card signed
ELE09-00053 Electrical Rough-In2/5/20092/5/20092/5/2009 3:46:24 PMPPASS
###-#### Internet Inspection Request from: Todd Holbrook ceiling ok
ELE09-00063 Electrical Rough-In2/4/20092/5/20092/5/2009 1:45:29 PMPPART
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL walls , hard ceilings anop
ELE08-02230 Permanent Service2/5/20092/5/20092/5/2009 1:21:09 PMPFAIL
linda Note: please call 1/2 hr prior to inspection to meet with Phone #: ###-####
corr. net owner300.4 shall provide bushings for #4 or larger where it enters panel, 312.5 needs plastic conn. for GEC that enters back of panel, shall use #1 alum SER , or install 90 amp max breaker for #2 alum SER, 250.94 needs grd for other services, phone & catv
ELE09-00178 Electrical Rough-In2/5/20092/5/20092/5/2009 1:04:57 PMPFAIL
Cover inspection, If possible to be done early, owner will not be available late afternoon Phone #: ###-#### Internet Inspection Request from: Jari Rivers
corr . called box fill nail plates and 11/4", grd wires cut short needs 6", outlet for wall space island counter, grd metal boxes, update permit for # of rms and p/s
ELE09-00189 Conference2/4/20092/5/20092/5/2009 9:57:53 AMADONE
need to do job on saterday, will have idaho power disconnect & reconnect on saterday. will have to have inspectors ok prior on work for idaho power reconnection on saterday. Phone #: ###-#### Internet Inspection Request from: Miles Berry
p/s will be ok for hook up on saterday
ELE09-00153 Electrical Rough-In2/4/20092/5/20092/5/2009 9:29:47 AMAPART
trent - wall Phone #: ###-#### walls ok
ELE09-00175 Electrical Rough-In2/4/20092/5/20092/5/2009 8:52:51 AMAPART
daryl Phone #: ###-#### wiring for x ray equipment shall meet requirements of
517 V. x-ray equipment walls ok