ELE09-01693
| ELE-Aging Inspection | 2/5/2010 | 2/5/2010 | 2/9/2010 11:19:11 AM | | DONE |
|
|
looked at signs, see final
|
ELE09-01624
| ELE-Aging Inspection | 2/5/2010 | 2/5/2010 | 2/9/2010 6:47:22 AM | | DONE |
|
|
suc
|
ELE07-03020
| ELE-Aging Inspection | 2/5/2010 | 2/5/2010 | 2/9/2010 5:35:07 AM | | DONE |
|
|
suc
|
ELE07-03867
| ELE-Aging Inspection | 2/5/2010 | 2/5/2010 | 2/9/2010 5:33:34 AM | | DONE |
|
|
no activity, see doc expire
|
ELE10-00212
| Temporary Service | 2/5/2010 | 2/5/2010 | 2/8/2010 9:23:15 AM | P | PASS |
|
|
Don ###-#### called, t/s u/g n ok
|
ELE10-00211
| Final | 2/5/2010 | 2/5/2010 | 2/8/2010 8:44:19 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams temp lights ok, signed structural card, no esc this project
|
ELE10-00215
| Electrical Rough-In | 2/5/2010 | 2/5/2010 | 2/8/2010 8:23:17 AM | P | FAIL |
|
|
Chris-Late this afternoon please Phone #: ###-#### called, left message, left correction notice, NECn300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 314.20 boxes shall be flush with finished surface on outside, BCC shall install boxes and panel before cover, shall see u/g before cover, NOTE: corrections shall be msde in 5 working days or further action will be taken
|
ELE09-01675
| Permanent Service | 2/5/2010 | 2/5/2010 | 2/5/2010 3:58:22 PM | P | FAIL |
|
|
Tyler Phone #: ###-#### called, left correction notice, NEC 312.5 all conductors entering enclosures shall have abrasion protection, BCC shall provide access for inspection
|
ELE09-00237
| Final | 2/5/2010 | 2/5/2010 | 2/5/2010 2:35:19 PM | P | FAIL |
|
|
Mike Phone #: ###-#### please call 30 min before going out left correction notice, NEC 110.26(A) shall provide workspace about panel per article, 410.16(C) closet lights shall be provided with clearance per article, NOTE corrections shall be made within 5 working days or further action will be taken
|
ELE09-01997
| Electrical Rough-In | 2/5/2010 | 2/5/2010 | 2/5/2010 2:13:02 PM | P | PART |
|
|
Underground only please - AS LATE IN AFTERNOON AS POSSIBLE PLEASE!! Thank you! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to cover u/g for carports and west side building, no esc this project
|
ELE10-00090
| Final | 2/5/2010 | 2/5/2010 | 2/5/2010 1:37:26 PM | A | PASS |
|
|
thanks! Phone #: ###-#### Internet Inspection Request from: Darryn Coburn called, ok to final
|
ELE09-01911
| Final | 2/4/2010 | 2/5/2010 | 2/5/2010 12:44:47 PM | A | PASS |
|
|
Donald- Phone #: ###-#### ok to final
|
ELE10-00102
| Final | 2/4/2010 | 2/5/2010 | 2/5/2010 10:44:03 AM | A | PASS |
|
|
Remodel final inspection Phone #: ###-#### Internet Inspection Request from: Zane Robertson ok to final
|
ELE10-00132
| Final | 2/4/2010 | 2/5/2010 | 2/5/2010 10:28:30 AM | A | PASS |
|
|
labeled breaker correctly - all power works on existing reception wall. Phone #: ###-#### Internet Inspection Request from: Andy Rose corrections made, ok to final,signed card, no esc this project
|
ELE10-00207
| Final | 2/4/2010 | 2/5/2010 | 2/5/2010 10:26:45 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Debby Ellis ok to final, signed occupancy card, no esc this project
|
ELE10-00091
| Final | 2/4/2010 | 2/5/2010 | 2/5/2010 10:04:42 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok to final, called structural, said ok to final electrical, signed card, no esc this project
|
ELE10-00004
| Permanent Service | 2/4/2010 | 2/5/2010 | 2/5/2010 9:29:34 AM | A | CANC |
|
|
Jared Phone #: ###-#### see conference
|
ELE10-00004
| Conference | 2/5/2010 | 2/5/2010 | 2/5/2010 9:29:16 AM | A | DONE |
|
|
Jared Phone #: ###-#### went over requirement for individual buildings by structural or can't have more than 1 service
|
ELE09-02310
| Electrical Rough-In | 2/4/2010 | 2/5/2010 | 2/5/2010 9:12:41 AM | A | PASS |
|
|
Jason Phone #: ###-#### ok to cover u/g , no esc this project
|
ELE09-02278
| Electrical Rough-In | 2/4/2010 | 2/5/2010 | 2/5/2010 8:52:29 AM | A | PART |
|
|
Contact: Tony Holt Phone #: ###-#### Internet Inspection Request from: Deb Gooden kitchen walls and hard lids except panel wall only ok to cover anop, no esc this project
|
ELE10-00165
| Conference | 2/3/2010 | 2/5/2010 | 2/5/2010 8:27:41 AM | A | DONE |
|
|
Cheryl Phone #: ###-#### met owner talked about 1/14" and new circuits and j-boxes, no esc this project
|