Inspections for the day of: Thursday, February 5, 2015.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01654 ELE-Aging Inspection2/5/20152/5/20152/6/2015 11:06:53 AM CANC
posted correction 2-6-15 11::05 am
GCE15-00018 GCE-Rough-In Permanent Service2/5/20152/5/20152/5/2015 3:54:32 PMPPASS
Brandon ###-####
RI ,Ok PS, UG, N, OK
ELE14-03166 Final2/4/20152/5/20152/5/2015 3:26:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Celinda Winters
Correction made final OK
ELE14-03237 Final2/5/20152/5/20152/5/2015 2:55:27 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
312.4 Drywall gap around box shall be no larger than 1/8 inch, unit 102
210.8.7 GFI protection required within six foot of sink unit 101 and 210
110.12 MEchanical execution of work, exhaust fan doesnt work unit 101
ELE14-03559 Permanent Service2/5/20152/5/20152/5/2015 2:06:28 PMPCANC
Phone #: ###-#### Inspection requested via web by daniel bibikov
Already done, contractor called by mistake
ELE14-03559 Permanent Service2/5/20152/5/20152/5/2015 2:05:58 PMPCANC
Phone #: ###-#### Inspection requested via web by daniel bibikov
Contractor called by mistake
ELE14-03369 Permanent Service2/5/20152/5/20152/5/2015 1:19:04 PMPPASS
Mark Phone #: ###-####
PS, OH, N, OK
ELE14-03369 Rough-In Permanent Service2/5/20152/5/20152/5/2015 1:18:55 PMPCANC
Mark Phone #: ###-####
Needed PS inspection
ELE14-03488 Electrical Rough-In2/5/20152/5/20152/5/2015 1:01:58 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
underground from east foundation wall across garage floor, 3 conduits, ok to cover
ELE15-00250 Rough-In Permanent Service2/4/20152/5/20152/5/2015 12:25:49 PMPPASS
Phone #: ###-#### Inspection requested via web by Zane Robertson
RI OK , PS, UG, N< OK
ELE15-00265 Electrical Rough-In2/4/20152/5/20152/5/2015 11:17:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Seth Stears
wall cover OK
ELE15-00302 Final2/4/20152/5/20152/5/2015 10:26:53 AMACANC
Please energize - Thank you! Phone #: ###-#### Inspection requested via web by Daniel Schaffeld
Needed temp service inspection
ELE15-00302 Temporary Service2/5/20152/5/20152/5/2015 10:26:31 AMPPASS
Please energize - Thank you! Phone #: ###-#### Inspection requested via web by Daniel Schaffeld
TS, UG, N, OK
ELE14-03457 Electrical Rough-In2/4/20152/5/20152/5/2015 10:12:03 AMAPASS
Need inspection to cover inside perimeter conduit. Phone #: ###-#### Inspection requested via web by Alan Lusk
OK to bury underground interior conduit around exterior perimeter, except for northeast corner closest to loading bay. Conduit under mandoor opening at loading bay stops underground and does not turn up out of floor
ELE14-03529 Final2/4/20152/5/20152/5/2015 9:49:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Cobur
Final OK
ELE14-03538 Final2/4/20152/5/20152/5/2015 9:49:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Final OK
GCE15-00017 GCE-Final2/4/20152/5/20152/5/2015 9:05:09 AMAFAIL
Alan ###-####
(B) Disconnecting Means. Each multiwire branch circuit
shall be provided with a means that will simultaneously
disconnect all ungrounded conductors at the point where
the branch circuit originates
408.4 every circuit shall be legibly identified
210.5 C ungrounded conductors shall be permanently identified
314.17 Conductors entering boxes shall be protected, wire entering service with no connector
ELE15-00284 Temporary Service2/4/20152/5/20152/5/2015 7:45:26 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn