ELE12-01654
| ELE-Aging Inspection | 2/5/2015 | 2/5/2015 | 2/6/2015 11:06:53 AM | | CANC |
|
|
posted correction 2-6-15 11::05 am
|
GCE15-00018
| GCE-Rough-In Permanent Service | 2/5/2015 | 2/5/2015 | 2/5/2015 3:54:32 PM | P | PASS |
|
|
Brandon ###-#### RI ,Ok PS, UG, N, OK
|
ELE14-03166
| Final | 2/4/2015 | 2/5/2015 | 2/5/2015 3:26:08 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters Correction made final OK
|
ELE14-03237
| Final | 2/5/2015 | 2/5/2015 | 2/5/2015 2:55:27 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov 312.4 Drywall gap around box shall be no larger than 1/8 inch, unit 102 210.8.7 GFI protection required within six foot of sink unit 101 and 210 110.12 MEchanical execution of work, exhaust fan doesnt work unit 101
|
ELE14-03559
| Permanent Service | 2/5/2015 | 2/5/2015 | 2/5/2015 2:06:28 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Already done, contractor called by mistake
|
ELE14-03559
| Permanent Service | 2/5/2015 | 2/5/2015 | 2/5/2015 2:05:58 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Contractor called by mistake
|
ELE14-03369
| Permanent Service | 2/5/2015 | 2/5/2015 | 2/5/2015 1:19:04 PM | P | PASS |
|
|
Mark Phone #: ###-#### PS, OH, N, OK
|
ELE14-03369
| Rough-In Permanent Service | 2/5/2015 | 2/5/2015 | 2/5/2015 1:18:55 PM | P | CANC |
|
|
Mark Phone #: ###-#### Needed PS inspection
|
ELE14-03488
| Electrical Rough-In | 2/5/2015 | 2/5/2015 | 2/5/2015 1:01:58 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton underground from east foundation wall across garage floor, 3 conduits, ok to cover
|
ELE15-00250
| Rough-In Permanent Service | 2/4/2015 | 2/5/2015 | 2/5/2015 12:25:49 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson RI OK , PS, UG, N< OK
|
ELE15-00265
| Electrical Rough-In | 2/4/2015 | 2/5/2015 | 2/5/2015 11:17:01 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Seth Stears wall cover OK
|
ELE15-00302
| Final | 2/4/2015 | 2/5/2015 | 2/5/2015 10:26:53 AM | A | CANC |
|
|
Please energize - Thank you! Phone #: ###-#### Inspection requested via web by Daniel Schaffeld Needed temp service inspection
|
ELE15-00302
| Temporary Service | 2/5/2015 | 2/5/2015 | 2/5/2015 10:26:31 AM | P | PASS |
|
|
Please energize - Thank you! Phone #: ###-#### Inspection requested via web by Daniel Schaffeld TS, UG, N, OK
|
ELE14-03457
| Electrical Rough-In | 2/4/2015 | 2/5/2015 | 2/5/2015 10:12:03 AM | A | PASS |
|
|
Need inspection to cover inside perimeter conduit. Phone #: ###-#### Inspection requested via web by Alan Lusk OK to bury underground interior conduit around exterior perimeter, except for northeast corner closest to loading bay. Conduit under mandoor opening at loading bay stops underground and does not turn up out of floor
|
ELE14-03529
| Final | 2/4/2015 | 2/5/2015 | 2/5/2015 9:49:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Cobur Final OK
|
ELE14-03538
| Final | 2/4/2015 | 2/5/2015 | 2/5/2015 9:49:24 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final OK
|
GCE15-00017
| GCE-Final | 2/4/2015 | 2/5/2015 | 2/5/2015 9:05:09 AM | A | FAIL |
|
|
Alan ###-#### (B) Disconnecting Means. Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates 408.4 every circuit shall be legibly identified 210.5 C ungrounded conductors shall be permanently identified 314.17 Conductors entering boxes shall be protected, wire entering service with no connector
|
ELE15-00284
| Temporary Service | 2/4/2015 | 2/5/2015 | 2/5/2015 7:45:26 AM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Inspection cancelled from web by: Darryn Coburn
|