Inspections for the day of: Wednesday, February 5, 2020.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00032 Final2/5/20202/5/20202/5/2020 2:51:34 PMPPASS
Please call Lynn prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor
Final ok
ELE19-04151 Final2/4/20202/5/20202/5/2020 2:12:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Danny Pardee
Listing and disconnecting means from existing. Final ok
ELE20-00383 Final2/4/20202/5/20202/5/2020 10:57:51 AMACANC
Key is located in front outlet Phone #: ###-#### Inspection requested via web by danny perrine Wrong job called in
ELE20-00384 Final2/4/20202/5/20202/5/2020 10:56:38 AMACANC
Key is located in front outlet Phone #: ###-#### Inspection requested via web by danny perrine Wrong job called in
ELE20-00271 Rough-In Permanent Service2/5/20202/5/20202/5/2020 10:55:10 AMAFAIL
Phone #: ###-#### Inspection requested via web by Troy Ballard
300.4- Nail plates shall be installed to protect NM cable where ran thru bored holes that do not maintain 1 1/4" from framing surface. To photo. 314.25- All boxes shall have covers installed completely covering openings. Check all recessed can junction box covers. 1 missing over stairs, several with gaps to boxes including tall ceiling.
352.48- Fitting securing PVC underground service entrance conduit to meter not glued.
408.7- Unused breaker spaces shall be closed by approved means.
ELE19-04473 Final2/5/20202/5/20202/5/2020 10:36:47 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
ELE19-00602 Electrical Rough-In2/3/20202/5/20202/4/2020 3:40:39 PMACANC
Underground cover for 5th street side historic pole lights. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Duplicate request.