ELE20-00032
| Final | 2/5/2020 | 2/5/2020 | 2/5/2020 2:51:34 PM | P | PASS |
|
|
Please call Lynn prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor Final ok
|
ELE19-04151
| Final | 2/4/2020 | 2/5/2020 | 2/5/2020 2:12:19 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Danny Pardee Listing and disconnecting means from existing. Final ok
|
ELE20-00383
| Final | 2/4/2020 | 2/5/2020 | 2/5/2020 10:57:51 AM | A | CANC |
|
|
Key is located in front outlet Phone #: ###-#### Inspection requested via web by danny perrine Wrong job called in
|
ELE20-00384
| Final | 2/4/2020 | 2/5/2020 | 2/5/2020 10:56:38 AM | A | CANC |
|
|
Key is located in front outlet Phone #: ###-#### Inspection requested via web by danny perrine Wrong job called in
|
ELE20-00271
| Rough-In Permanent Service | 2/5/2020 | 2/5/2020 | 2/5/2020 10:55:10 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Troy Ballard 300.4- Nail plates shall be installed to protect NM cable where ran thru bored holes that do not maintain 1 1/4" from framing surface. To photo. 314.25- All boxes shall have covers installed completely covering openings. Check all recessed can junction box covers. 1 missing over stairs, several with gaps to boxes including tall ceiling. 352.48- Fitting securing PVC underground service entrance conduit to meter not glued. 408.7- Unused breaker spaces shall be closed by approved means.
|
ELE19-04473
| Final | 2/5/2020 | 2/5/2020 | 2/5/2020 10:36:47 AM | A | PASS |
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
|
ELE19-00602
| Electrical Rough-In | 2/3/2020 | 2/5/2020 | 2/4/2020 3:40:39 PM | A | CANC |
|
|
Underground cover for 5th street side historic pole lights. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Duplicate request.
|