Inspections for the day of: Wednesday, February 5, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00412 Rough-In Permanent Service2/5/20202/5/20202/5/2020 2:26:40 PMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok to cover p/s u/g n ok
ELE20-00413 Rough-In Permanent Service2/5/20202/5/20202/5/2020 2:26:11 PMPPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok p/s u/g n ok
ELE19-04579 Final2/5/20202/5/20202/5/2020 1:17:53 PMPPASS
preferably after 1pm Phone #: ###-#### Inspection requested via web by David McClellan final ok
ELE19-04600 Final2/5/20202/5/20202/5/2020 12:54:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt corrections made final ok
ELE17-03713 ELE-Aging Inspection2/5/20202/5/20202/5/2020 11:11:01 AM DONE
As per previous phone call. Project is ongoing.
ELE19-04944 Final2/4/20202/5/20202/5/2020 11:07:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
ELE20-00202 Electrical Rough-In2/4/20202/5/20202/5/2020 9:59:58 AMAPASS
Good afternoon, we have addresses the shoddy staple work. Flat cables are now stalled flat, stackers have been installed at busy locations, and general quality of sta pl ling has been corrected. Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings Corrections made Master bed, Laundry room, Living room and Kitchen ok to cover.
ELE20-00406 Final2/4/20202/5/20202/5/2020 9:50:51 AMAFAIL
Contact: Matt Cinko Phone #: ###-#### Inspection requested via web by Deb Gooden 110.26D Lighting around panel boards shall not be controlled by automatic means. 440.22C Protective devices shall not exceed manufacturers values. (40A max nameplate 45A installed)
ELE19-04600 Final2/4/20202/5/20202/5/2020 9:36:37 AMAFAIL
Please call miguel Phone #: ###-#### Inspection requested via web by Greg Traudt 314.20 Boxes set back 1/4in shall have extension ring(Front and back W/P receps) 314.25 All boxes and devices shall have cover plates(Pantry switch) 406.5 Receps shall be securely fastened(Front and back W/P receps)