ELE20-00412
| Rough-In Permanent Service | 2/5/2020 | 2/5/2020 | 2/5/2020 2:26:40 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok to cover p/s u/g n ok
|
ELE20-00413
| Rough-In Permanent Service | 2/5/2020 | 2/5/2020 | 2/5/2020 2:26:11 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson rough in ok p/s u/g n ok
|
ELE19-04579
| Final | 2/5/2020 | 2/5/2020 | 2/5/2020 1:17:53 PM | P | PASS |
|
|
preferably after 1pm Phone #: ###-#### Inspection requested via web by David McClellan final ok
|
ELE19-04600
| Final | 2/5/2020 | 2/5/2020 | 2/5/2020 12:54:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt corrections made final ok
|
ELE17-03713
| ELE-Aging Inspection | 2/5/2020 | 2/5/2020 | 2/5/2020 11:11:01 AM | | DONE |
|
|
As per previous phone call. Project is ongoing.
|
ELE19-04944
| Final | 2/4/2020 | 2/5/2020 | 2/5/2020 11:07:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
ELE20-00202
| Electrical Rough-In | 2/4/2020 | 2/5/2020 | 2/5/2020 9:59:58 AM | A | PASS |
|
|
Good afternoon, we have addresses the shoddy staple work. Flat cables are now stalled flat, stackers have been installed at busy locations, and general quality of sta pl ling has been corrected. Thank you, Dan Phone #: ###-#### Inspection requested via web by Dan Jennings Corrections made Master bed, Laundry room, Living room and Kitchen ok to cover.
|
ELE20-00406
| Final | 2/4/2020 | 2/5/2020 | 2/5/2020 9:50:51 AM | A | FAIL |
|
|
Contact: Matt Cinko Phone #: ###-#### Inspection requested via web by Deb Gooden 110.26D Lighting around panel boards shall not be controlled by automatic means. 440.22C Protective devices shall not exceed manufacturers values. (40A max nameplate 45A installed)
|
ELE19-04600
| Final | 2/4/2020 | 2/5/2020 | 2/5/2020 9:36:37 AM | A | FAIL |
|
|
Please call miguel Phone #: ###-#### Inspection requested via web by Greg Traudt 314.20 Boxes set back 1/4in shall have extension ring(Front and back W/P receps) 314.25 All boxes and devices shall have cover plates(Pantry switch) 406.5 Receps shall be securely fastened(Front and back W/P receps)
|