Inspections for the day of: Tuesday, February 6, 2001.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD00-01772 FIRE-Final Inspection2/5/20012/6/20012/6/2001 12:00:00 AMAPASS
###-####
FIR00-00289 INSP-Final Inspection2/5/20012/6/20012/6/2001 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 02/05/2001 at 12:37:37. Contact: ###-####. pump suction at negative during 150% flow test. UW at test also. 4000gpms available at 20 psi. above 4000 gpms the pump has negative suction 2/7/2001 9:26:44 AM
BLD99-01727 FIRE-Final Inspection2/5/20012/6/20012/6/2001 12:00:00 AMPPASS
Scheduled by Inspector: 409 On 2/5/2001 2:26:14 PM
FIR00-00672 INSP-Final Inspection2/6/20012/6/20012/6/2001 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 02/06/2001 at 09:21:24. Contact: ###-####.
BLD00-02037 FIRE-Final Inspection2/6/20012/6/20012/6/2001 12:00:00 AMPPASS
###-####