Inspections for the day of: Friday, February 6, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03339 Final2/4/20042/6/20042/6/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 2/4/2004 at 9:00:25 AM. Contact: ###-####. 410.8 needs shelf and rod installed in closet and fixture , so clearence can be checked 2/6/2004 9:35:48 AM
ELE04-00319 Rough-In Permanent Service2/4/20042/6/20042/6/2004 12:00:00 AMAPASS
allen-- ###-#### r/i ok
p/s u/g new ok 2/6/2004 9:03:14 AM
ELE04-00311 Permanent Service2/5/20042/6/20042/6/2004 12:00:00 AMANH
New service is on detached garage in back, owner says okay to go in; Phone #: ###-#### Internet Inspection Request from: Andy Rose
notice posted called 2/6/2004 10:08:08 AM
ELE04-00101 Final2/5/20042/6/20042/6/2004 12:00:00 AMPNR
We need a partial final if at all possible for walls.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas not ready called 2/6/2004 12:55:35 PM
ELE03-03676 Final2/6/20042/6/20042/6/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 2/6/2004 at 7:40:55 AM. Contact: ###-####. cor. posted called 210.52(C) needs outlet right of kit. sink, 210.8 needs gfci or single device outlet garage right of furnace 2/6/2004 2:05:20 PM
ELE04-00338 Rough-In Permanent Service2/6/20042/6/20042/6/2004 12:00:00 AMPFAIL
###-####- rick called shall wire dinning/ study, on small appliance branch circuit 210.52(B) states or have approved plans at job site stating room is a study only 2/6/2004 2:33:28 PM
ELE04-00032 Permanent Service2/6/20042/6/20042/6/2004 12:00:00 AMPFAIL
roy; Phone #: ###-#### Internet Inspection Request from: Annette Moore called correction not made 2/6/2004 4:15:48 PM
ELE04-00315 Permanent Service2/6/20042/6/20042/6/2004 12:00:00 AMPFAIL
mark; Phone #: ###-#### Internet Inspection Request from: Annette Moore no cor. posted electrician angry and left job called contractor met with Dan K of Power PLus and resloved problems contractor will reschedule inspection when corrections made GEC shall be at p/s not sub panel, shall not pass GEC in feeder raceway to sub panel and pass through sub panel shall remove feeder to sub panel from mwtwer enclousure,, shall not ID #6 or smaller equip grd 2/6/2004 3:52:36 PM