ELE05-01308
| ELE-Aging Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 4:59:26 PM | | DONE |
|
|
called cont, suc
|
ELE06-00339
| Rough-In Permanent Service | 2/6/2006 | 2/6/2006 | 2/6/2006 4:25:15 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire called contr, told them that gec still needed abrasion protection, 1 box not made up in kitchen, metal box in kitchen ceiling shall be grounded, and that there didn't appear to be a circuit for the furnace. ric ok, p/s u/g n ok
|
ELE05-04046
| ELE-Aging Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 3:56:58 PM | | DONE |
|
|
see final
|
ELE06-00381
| Temporary Service | 2/1/2006 | 2/6/2006 | 2/6/2006 3:55:43 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Tina Payne met contr, left corr notice, 230.24(B)(4) conductors shall have minimum 18' over public parking areas, 312.5 conductors entering enclosures shall have abrasion protection, 112.12(A) unused openings shall be closed in panel, 408.4 circuit directory shall be provided, 408.7 unused breaker openings shall be closed, 400.5(A) max current for 6/4 soow cord shall be 45 amps, note: line and load at breaker at transformer shall be line at top, load at bottom of breaker
|
ELE06-00415
| Electrical Rough-In | 2/6/2006 | 2/6/2006 | 2/6/2006 2:39:04 PM | P | PASS |
|
|
trench inspection on the corner of Five Mile and Emerald; Phone #: ###-#### Internet Inspection Request from: Dana Moyer u/g ok to cover
|
ELE04-00946
| Electrical Rough-In | 2/6/2006 | 2/6/2006 | 2/6/2006 2:22:27 PM | P | PASS |
|
|
phil; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, told to add nailplates,description for outlet spacing sounds ok. ric kitchen ok
|
ELE06-00402
| Permanent Service | 2/6/2006 | 2/6/2006 | 2/6/2006 1:54:46 PM | P | PASS |
|
|
p/s reconnect ok
|
ELE05-00617
| ELE-Aging Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 9:45:37 AM | | DONE |
|
|
see final
|
ELE06-00402
| Permanent Service | 2/3/2006 | 2/6/2006 | 2/6/2006 9:22:15 AM | A | CANC |
|
|
Andy -- AM conference and PM permanent service inspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong see pm
|
ELE06-00402
| Conference | 2/3/2006 | 2/6/2006 | 2/6/2006 9:09:40 AM | A | DONE |
|
|
Andy -- AM conference and PM permanent service inspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong reviewed service change, add ground rods, change nipple to new panel
|
ELE06-00324
| Electrical Rough-In | 2/3/2006 | 2/6/2006 | 2/6/2006 9:08:29 AM | A | CANC |
|
|
UNDERGROUND PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy wrong address, already done about a week ago.
|
ELE06-00369
| Electrical Rough-In | 2/3/2006 | 2/6/2006 | 2/6/2006 8:49:03 AM | A | CANC |
|
|
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy see rip
|
ELE06-00369
| Rough-In Permanent Service | 2/6/2006 | 2/6/2006 | 2/6/2006 12:00:00 AM | A | PASS |
|
|
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ric ok, p/s u/g n ok
|
ELE05-00617
| Final | 2/6/2006 | 2/6/2006 | 2/6/2006 12:00:00 AM | P | PASS |
|
|
ok to final
|
ELE05-04046
| Final | 2/6/2006 | 2/6/2006 | 2/6/2006 12:00:00 AM | P | PASS |
|
|
looked at sign, ok to final
|
ELE06-02976
| ELE-Request for Extension | 2/5/2007 | 2/6/2006 | | A | |
|
|
pls extend
|