Inspections for the day of: Monday, February 6, 2006.
Number of inspections: 16
Percentage of inspections complete: 94 %
Percentage of inspections not complete: 6 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01308 ELE-Aging Inspection2/6/20062/6/20062/6/2006 4:59:26 PM DONE
called cont, suc
ELE06-00339 Rough-In Permanent Service2/6/20062/6/20062/6/2006 4:25:15 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Danette Brookshire called contr, told them that gec still needed abrasion protection, 1 box not made up in kitchen, metal box in kitchen ceiling shall be grounded, and that there didn't appear to be a circuit for the furnace. ric ok, p/s u/g n ok
ELE05-04046 ELE-Aging Inspection2/6/20062/6/20062/6/2006 3:56:58 PM DONE
see final
ELE06-00381 Temporary Service2/1/20062/6/20062/6/2006 3:55:43 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Tina Payne met contr, left corr notice, 230.24(B)(4) conductors shall have minimum 18' over public parking areas, 312.5 conductors entering enclosures shall have abrasion protection, 112.12(A) unused openings shall be closed in panel, 408.4 circuit directory shall be provided, 408.7 unused breaker openings shall be closed, 400.5(A) max current for 6/4 soow cord shall be 45 amps, note: line and load at breaker at transformer shall be line at top, load at bottom of breaker
ELE06-00415 Electrical Rough-In2/6/20062/6/20062/6/2006 2:39:04 PMPPASS
trench inspection on the corner of Five Mile and Emerald; Phone #: ###-#### Internet Inspection Request from: Dana Moyer u/g ok to cover
ELE04-00946 Electrical Rough-In2/6/20062/6/20062/6/2006 2:22:27 PMPPASS
phil; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, told to add nailplates,description for outlet spacing sounds ok. ric kitchen ok
ELE06-00402 Permanent Service2/6/20062/6/20062/6/2006 1:54:46 PMPPASS
p/s reconnect ok
ELE05-00617 ELE-Aging Inspection2/6/20062/6/20062/6/2006 9:45:37 AM DONE
see final
ELE06-00402 Permanent Service2/3/20062/6/20062/6/2006 9:22:15 AMACANC
Andy -- AM conference and PM permanent service inspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong see pm
ELE06-00402 Conference2/3/20062/6/20062/6/2006 9:09:40 AMADONE
Andy -- AM conference and PM permanent service inspection; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong reviewed service change, add ground rods, change nipple to new panel
ELE06-00324 Electrical Rough-In2/3/20062/6/20062/6/2006 9:08:29 AMACANC
UNDERGROUND PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy wrong address, already done about a week ago.
ELE06-00369 Electrical Rough-In2/3/20062/6/20062/6/2006 8:49:03 AMACANC
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy see rip
ELE06-00369 Rough-In Permanent Service2/6/20062/6/20062/6/2006 12:00:00 AMAPASS
PAUL; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ric ok, p/s u/g n ok
ELE05-00617 Final2/6/20062/6/20062/6/2006 12:00:00 AMPPASS
ok to final
ELE05-04046 Final2/6/20062/6/20062/6/2006 12:00:00 AMPPASS
looked at sign, ok to final
ELE06-02976 ELE-Request for Extension2/5/20072/6/2006 A 
pls extend