FIR05-00643
| INSP-Final Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 12:13:21 PM | P | PASS |
|
|
Inspection passed, permit finaled.
|
FIR05-00531
| INSP-Final Inspection | 2/3/2006 | 2/6/2006 | 2/6/2006 12:09:43 PM | A | DEFR |
|
|
Require approved resubmitted plans for the AHU addresses and changed av location for verification prior to final.
|
FIR05-00520
| INSP-Final Inspection | 2/3/2006 | 2/6/2006 | 2/6/2006 12:06:54 PM | A | DEFR |
|
|
Final pending the completion and final of the shell fire sprinkler permit FIR05-00372.
|
BLD06-00047
| FIRE-Final Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 11:23:25 AM | P | PASS |
|
|
Items on correction notice are complete, fire life safety passed inspection.
|
BLD05-03044
| FIRE-Final Inspection | 2/3/2006 | 2/6/2006 | 2/6/2006 11:21:38 AM | A | PASS |
|
|
Permit related corrections have been completed, inspection passed.
|
FIR06-00089
| INSP-Final Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 11:20:12 AM | P | PASS |
|
|
Fire alarm finaled.
|
FIR05-00899
| INSP-Final Inspection | 2/6/2006 | 2/6/2006 | 2/6/2006 11:17:05 AM | P | PASS |
|
|
c/n items are complete, inspection passed.
|
FIR06-00089
| INSP-Alarm Testing | 2/6/2006 | 2/6/2006 | 2/6/2006 11:10:46 AM | P | PASS |
|
|
Fire alarm work passed field inspection.
|
FIR05-00594
| INSP-Sprinkler Rough-in | 2/3/2006 | 2/6/2006 | 2/6/2006 10:22:34 AM | A | PART |
|
|
First floor entry lobby hard lid area inspection only, acceptable to cover at this location only. The 1 1/4 branch line to feed the elevator pit sprinklers has not been installed.
|