Inspections for the day of: Tuesday, February 6, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00479 INSP-Final Inspection2/6/20072/6/20072/6/2007 5:34:05 PMPFAIL
Per Brian the first floor and second floors are now complete. Third and fourth floors will be started tomorrow.
BLD06-01694 FIRE-Final Inspection2/6/20072/6/20072/6/2007 4:14:06 PMPFAIL
Need suite number, fire extinguisher and the doors/hardware installed.
FIR06-00874 INSP-Sprinkler Rough-in2/6/20072/6/20072/6/2007 3:51:00 PMPFAIL
Inspection was for just the office areas not the pre-action area. The office areas can not be covered yet due to insulation falling from the deck and creating obstructions to the upright sprinkler heads. Also an upright needs to be added in the west restroom due to an overspacing issue. The plans need to be resubmitted to the city for approval due to the amount of additional upright heads on the pre-action system. Many of these heads are in the hydraulic remote area.
FIR07-00004 INSP-Final Inspection2/6/20072/6/20072/6/2007 3:19:03 PMPFAIL
Need ceiling tile installed and approved plans on site for me to verify that what is should be.
FIR07-00079 INSP-Sprinkler Rough-in2/5/20072/6/20072/6/2007 3:08:08 PMAFAIL
I stopped at this project twice today. The first time the job shack was locked up and the general contractor and fire sprinkler contractor were not here. The second time I stopped the general contractor was here but he did not have the approved underground plans. He called Shilo and they faxed over unstamped drawings as I waited. I left after telling the general contractor not to cover the trench and to get the approved plans on site.
BLD05-03068 FIRE-Final Inspection2/6/20072/6/20072/6/2007 1:38:32 PMPFAIL
Life safety finaled - fire dept access road still an issue per troy
FIR06-00592 INSP-Final Inspection2/6/20072/6/20072/6/2007 1:13:15 PMPPASS
Permit finaled
FIR06-00957 INSP-Sprinkler Rough-in2/5/20072/6/20072/6/2007 12:44:24 PMAPART
The second floor of C wing will be ok to cover when the insulation is installed between the walls and the drop downs to the dry sidewalls. Also one pendant is overspaced as marked on the plans. C wing attic dry system 200 lb hydro test passed.
FIR06-00749 INSP-Final Inspection2/6/20072/6/20072/6/2007 12:29:26 PMAPASS
permit finaled
FIR06-00929 INSP-Final Inspection2/5/20072/6/20072/6/2007 11:02:38 AMAPART
ceilings are ok to cover but a ceiling or the walls will need to extend to the deck in the mechanical room and there will need to be a separation at the coolers as well.
BLD05-01295 FIRE-Final Inspection2/5/20072/6/20072/6/2007 10:39:16 AMAFAIL
It does not appear that any notes were read as requested on the previous inspection. Exit signs are missing at the main exits. Existing exit lights are inoperative. Closures have not been installed. Occupant load sign has not been provided. Knox box is not provided and so on.
BLD06-00995 FIRE-Final Inspection2/6/20072/6/20072/6/2007 8:44:28 AMPPASS
Life safety finaled
BLD06-00996 FIRE-Final Inspection2/5/20072/6/20072/6/2007 8:39:53 AMAPART
Temp only. Life safety will be ok to final when fire alarm permit for building B is complete.
BLD06-00993 FIRE-Final Inspection2/5/20072/6/20072/6/2007 8:36:33 AMAPASS
Life safety passed
FIR06-00922 INSP-Final Inspection2/5/20072/6/20072/6/2007 8:35:36 AMAPART
Temp only until building B is complete
FIR06-00925 INSP-Final Inspection2/5/20072/6/20072/6/2007 8:34:44 AMAPASS
permit finaled
FIR06-00923 INSP-Final Inspection2/5/20072/6/20072/6/2007 8:33:42 AMAPASS
permit finaled
FIR05-00738 INSP-Final Inspection2/5/20072/6/20072/5/2007 4:44:17 PMAPASS
Fire sprinkler permit finaled.