Inspections for the day of: Wednesday, February 6, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-02967 FIRE-Final Inspection2/5/20082/6/20082/6/2008 4:48:48 PMPNR
Not ready for final at this time per contractor.
FIR07-00662 INSP-Alarm Testing2/5/20082/6/20082/6/2008 4:48:09 PMAPART
Corrections noted at the previous inspection including a/v and pull station locations and non-functional sounder bases at three rooms verified for completion. FACP phone lines, batteries, AC power, SD above panel, and first floor nac tested okay. Notification devices for the 1st thru 4th floors tested - noted lacking coverage at the first floor vending/ice room, dB above 110 at two public restrooms (corrected while on site), a/v at the maintenance managers office on the 3rd floor does not function, sounder bases at three rooms 236, 336,and 436 do not function on general alarm. Also tested initating devices for the 1st and 2nd floors (manual pull stations and SD's only). Need to provide access for visual inspection of FSD functionality at some areas. Still need to test 3rd and 4th floor alarm initiation, elevator recall at both cars, 3rd and 4th floor nac panels, and check account and signal reciept information.
BLD07-03067 FIRE-Final Inspection2/6/20082/6/20082/6/2008 12:49:10 PMPPASS
Fire life safety inspection completed satisfactory.
FIR07-01026 INSP-Final Inspection2/5/20082/6/20082/6/2008 12:48:12 PMPFAIL
Offices at some locations are overspaced due to room construction not meeting the criteria for the "small room" rule.
FIR07-00896 INSP-Final Inspection2/5/20082/6/20082/6/2008 12:44:30 PMPPASS
Fire sprinkler permit finaled.
FIR08-00025 INSP-Sprinkler Rough-in2/5/20082/6/20082/6/2008 12:43:35 PMPPART
See red-lined areas on city stamped plan set for overhead rough-in locations approved for cover, noted two heads at the entry vestibule to be changed to QR, and two drops not yet installed.
FIR08-00037 INSP-Sprinkler Rough-in2/5/20082/6/20082/6/2008 11:51:30 AMAPART
See approved plans for areas circled and initialed as okay for cover at the hard lid ceilings, be aware of possible light fixture obstructions due to surface mounted lights not installed at this time.
BLD08-00203 FIRE-Final Inspection2/5/20082/6/20082/6/2008 11:49:40 AMAPASS
Fire life safety is acceptable, noted signage at the main entry/exit door "door to remain unlocked while building is occupied" to be posted proir to structural final for verification of compliance.
FIR08-00046 INSP-Final Inspection2/6/20082/6/20082/6/2008 12:00:00 AMPFAIL
Strobes in the men's and woman's restrooms did not function.All other devices on 2nd floor worked correctly. KR