BLD08-01656
| FIRE-Conference | 2/6/2009 | 2/6/2009 | 2/6/2009 4:13:48 PM | A | DONE |
|
|
I went over inspection procedures and order of completion with the superintendant.
|
FIR08-00791
| INSP-Final Inspection | 2/6/2009 | 2/6/2009 | 2/6/2009 4:12:48 PM | P | FAIL |
|
|
Not all of the sprinkler work is complete. Forward flush passed. Tim Frost is ok with the relocation of the PIV from the landscape/island to the exterior wall. The electric alarm bell is missing.
|
FIR08-00779
| INSP-Final Inspection | 2/6/2009 | 2/6/2009 | 2/6/2009 4:10:58 PM | P | FAIL |
|
|
The original panel was replaced after it was blown up due to high voltage backfeed from the ansul suppression system. The duct smoke detectors did not shut down the hvac units. The backflow preventor tamper switch needs to be on a separate zone which will cause modifications to the existing zone arrangement. As-builts are required but plan resubmittals are not. An updated map for the facp is required as well. The system will need to be retested once the zones have been redone.
|
FIR08-00852
| INSP-Final Inspection | 2/6/2009 | 2/6/2009 | 2/6/2009 4:07:02 PM | P | FAIL |
|
|
The front hood suppression system installation is not complete yet. No testing was performed.
|
FIR09-00018
| INSP-Sprinkler Rough-in | 2/3/2009 | 2/6/2009 | 2/6/2009 4:05:41 PM | P | PASS |
|
|
See the approved plans for locations where the sprinkler piping can be covered. I noted two quick responce upright heads that will need to be changed to standard responce and the earthquake bracing attacments are not utilizing through bolts as required per NFPA 13 for wood members.
|
BLD08-02584
| FIRE-Final Inspection | 2/6/2009 | 2/6/2009 | 2/6/2009 2:27:26 PM | P | PASS |
|
|
Life safety passed
|
BLD08-02585
| FIRE-Final Inspection | 2/6/2009 | 2/6/2009 | 2/6/2009 2:27:08 PM | P | PASS |
|
|
Life safety passed
|
BLD08-02583
| FIRE-Final Inspection | 2/6/2009 | 2/6/2009 | 2/6/2009 2:26:50 PM | P | PASS |
|
|
Life safety passed
|
BLD08-02036
| FIRE-Final Inspection | 2/4/2009 | 2/6/2009 | 2/6/2009 12:01:51 PM | A | CANC |
|
|
No inspection was performed due to the project related fire alarm not being complete.
|
FIR08-00757
| INSP-Final Inspection | 2/5/2009 | 2/6/2009 | 2/6/2009 12:01:20 PM | A | FAIL |
|
|
Per Scotty the project is not ready for inspection.
|
FIR08-00864
| INSP-Sprinkler Rough-in/Hydro | 2/5/2009 | 2/6/2009 | 2/6/2009 10:19:58 AM | A | FAIL |
|
|
Provide a hydro test for the new portion of the sprinkler system since it includes 22 sprinkler heads and can be isolated. Provide as-builts showing the piping changes and the additional pendants in the remote area. Replace the flat face(hex)bushings and provide on piece reducing fittings. Provide access to the inside of the coolers to verify storage heights and sprinkler obstructions. Provide verification of the annual inspection on the sprinkler system.
|
FIR08-00864
| INSP-Sprinkler Rough-in | 2/5/2009 | 2/6/2009 | 2/5/2009 3:08:48 PM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick
|