Inspections for the day of: Monday, February 6, 2012.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD12-00045 FIRE-Final Inspection2/6/20122/6/20122/6/2012 3:47:40 PMPPASS
life safety passed
FIR12-00014 INSP-Sprinkler Rough-in2/6/20122/6/20122/6/2012 3:42:06 PMPPASS
Permit finaled
BLD11-02165 FIRE-Final Inspection2/6/20122/6/20122/6/2012 3:20:49 PMAFAIL
Provide correct installation of the roof mounted duct smoke detector. Include ventilation in the housing as discussed.
BLD11-02165 FIRE-Alarm Testing2/6/20122/6/20122/6/2012 3:13:42 PMPFAIL
Provide correct installation of the roof mounted duct smoke detector. Include ventilation in the housing as discussed.
FIR11-00641 INSP-Final Inspection2/6/20122/6/20122/6/2012 3:12:38 PMPPASS
Permit finaled
FIR11-00543 INSP-Sprinkler Rough-in2/6/20122/6/20122/6/2012 3:07:19 PMPPASS
See the as-builts for locations where additional piping can be covered by hard lids.
FIR11-00671 INSP-Sprinkler Rough-in2/3/20122/6/20122/6/2012 2:39:25 PMAPART
Part of the rough-in passed but others failed. There are two area of concern where additional fittings have been added and as requested by the approval notes plans will need to be resubmitted. Upright sprinkler protection is overspaced above the slatted ceiling at the north end of the store. A hydro test is also required.
FIR11-00607 INSP-Sprinkler Rough-in2/3/20122/6/20122/6/2012 2:35:53 PMAPASS
Hard lid areas are ok to cover.
FIR11-00544 INSP-Supply line flush2/3/20122/6/20122/6/2012 11:24:28 AMAPASS
Underground supply line flush passed. On walking through the project I noted alot of painted sprinkler pendants that will require replacement.
FIR11-00215 INSP-Final Inspection2/1/20122/6/20122/6/2012 9:49:27 AMAPASS
Permit finaled. Suppression system functioned correctly.
BLD11-02750 FIRE-Final Inspection2/3/20122/6/20122/6/2012 9:34:20 AMAPASS
life safety passed
BLD11-02749 FIRE-Final Inspection2/3/20122/6/20122/6/2012 9:33:41 AMAPASS
life safety passed
FIR12-00025 INSP-Final Inspection2/2/20122/6/20122/6/2012 9:32:38 AMAPASS
Permit finaled. I found two strobes that were overspaced that were relocated as I waited. Also the sample tubes in one of the three duct smoke detectors had been installed backwards. THis was also corrected as I waited.
FIR11-00683 INSP-Alarm Testing2/3/20122/6/20122/3/2012 10:35:47 AMACANC
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
FIR11-00688 INSP-Alarm Testing2/3/20122/6/20122/3/2012 10:35:32 AMACANC
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate
FIR11-00688 INSP-Sprinkler Rough-in/Hydro2/3/20122/6/20122/3/2012 9:28:50 AMACANC
Phone #: ###-#### >> Inspection requested via web by Clint Tate Inspection cancelled from web by: Clint Tate