Inspections for the day of: Wednesday, February 6, 2013.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02982 Conference2/5/20132/6/20132/7/2013 1:32:35 PMADONE
Tony King Phone #: ###-#### Discussed fire protection of generator feed to fire pump and how conduits are prerun. To be installed separate from normal power conduits and identified in red and signage as per code.
ELE12-02887 Final2/6/20132/6/20132/6/2013 2:33:49 PMPFAIL
kyle Phone #: ###-#### Finish labelling panels. Label 480v panel in server room. Floor outlet covers not installed. KO seal and label 400a disconnect
ESC12-01217 General Inspection2/6/20132/6/20132/6/2013 1:14:20 PM FAIL
8-17-02.1 H Material tracked out onto roadway. Will reinspect Friday 2-8-12. Spoke to RP and he will clean up daily
ELE13-00250 Permanent Service2/5/20132/6/20132/6/2013 12:24:21 PMPPASS
Cal Phone #: ###-#### >> Inspection requested via web by cal crosby p/s o/h rec ok
ELE13-00153 Conference2/5/20132/6/20132/6/2013 10:50:13 AMADONE
greg Phone #: ###-#### Discussed code requirements for kitchen remodel. Nail plates, receptical spacing, and stapling
ELE12-03099 Final2/6/20132/6/20132/6/2013 10:06:49 AMAPASS
Please call Jim (###-####) 30 min ahead for access Phone #: ###-#### >> Inspection requested via web by Brad Girard Final ok
ELE13-00247 Electrical Rough-In2/5/20132/6/20132/6/2013 9:45:01 AMAPASS
would like to do this at 9:30 Call me a little before, I have codes to get up to 15th floor. Owner will be there to let us in. Phone #: ###-#### >> Inspection requested via web by Kurt Carlson Misc electrical adds rough in ok cover
ELE11-01990 ELE-Aging Inspection2/6/20132/6/20132/6/2013 9:12:42 AM DONE
Drove by not home