ELE11-00528
| ELE-Aging Inspection | 2/6/2014 | 2/6/2014 | 2/6/2014 4:38:35 PM | | DONE |
|
|
Waiting on owner
|
ELE10-02651
| ELE-Aging Inspection | 2/6/2014 | 2/6/2014 | 2/6/2014 4:16:24 PM | | DONE |
|
|
Waiting on owner
|
ELE11-01990
| ELE-Aging Inspection | 2/6/2014 | 2/6/2014 | 2/6/2014 3:51:23 PM | | DONE |
|
|
Waiting on owner
|
ELE14-00291
| Temporary Service | 2/6/2014 | 2/6/2014 | 2/6/2014 3:15:40 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00293
| Temporary Service | 2/6/2014 | 2/6/2014 | 2/6/2014 3:02:34 PM | P | PASS |
|
|
ALL 5 TEMPS ARE READY NOW Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00290
| Temporary Service | 2/6/2014 | 2/6/2014 | 2/6/2014 2:52:41 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00289
| Temporary Service | 2/6/2014 | 2/6/2014 | 2/6/2014 2:33:32 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00288
| Temporary Service | 2/6/2014 | 2/6/2014 | 2/6/2014 2:17:44 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE14-00242
| Conference | 2/5/2014 | 2/6/2014 | 2/6/2014 1:26:38 PM | A | DONE |
|
|
David Phone #: ###-#### Discussed replacing wiring around living room and required receptical layout. Not all walls accessible. Owner will do what he can to comply with layout.
|
ELE13-03441
| Electrical Rough-In | 2/6/2014 | 2/6/2014 | 2/6/2014 12:39:52 PM | A | PASS |
|
|
Ceiling cover. Danny onsite Phone #: ###-#### >> Inspection requested via web by Buster Bowen Ceiling grid rough in ok cover
|
ELE14-00018
| Electrical Rough-In | 2/6/2014 | 2/6/2014 | 2/6/2014 10:10:31 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Mark M Ceiling grid rough in ok cover
|
ELE13-03022
| Final | 2/5/2014 | 2/6/2014 | 2/6/2014 10:09:48 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.8- All garage 120 volt 15 and 20 amp recepticals shall have GFCI protection. 406.5- Switches and recepticals shall have faceplates installed. 406.4- Receptical yoke shall be rigidly mounted to box or box cover. 314.20- Boxes set back 1/4" or more shall have spark or extension ring.
|
ELE13-02929
| Final | 2/5/2014 | 2/6/2014 | 2/6/2014 9:45:56 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.8- All receptical outlets serving counter top space in kitchen shall have GFCI protection. 210.12- All bedroom outlets shall have AFCI protection. 1 arc won't trip. Patio lights not working, unable to test for arc protection.
|
ELE14-00285
| Final | 2/5/2014 | 2/6/2014 | 2/6/2014 8:52:50 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Needed rough in inspection
|
ELE14-00285
| Rough-In Permanent Service | 2/6/2014 | 2/6/2014 | 2/6/2014 8:52:48 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|
ELE14-00285
| Rough-In Permanent Service | 2/6/2014 | 2/6/2014 | 2/6/2014 8:52:35 AM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
|