Inspections for the day of: Thursday, February 6, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-00528 ELE-Aging Inspection2/6/20142/6/20142/6/2014 4:38:35 PM DONE
Waiting on owner
ELE10-02651 ELE-Aging Inspection2/6/20142/6/20142/6/2014 4:16:24 PM DONE
Waiting on owner
ELE11-01990 ELE-Aging Inspection2/6/20142/6/20142/6/2014 3:51:23 PM DONE
Waiting on owner
ELE14-00291 Temporary Service2/6/20142/6/20142/6/2014 3:15:40 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE14-00293 Temporary Service2/6/20142/6/20142/6/2014 3:02:34 PMPPASS
ALL 5 TEMPS ARE READY NOW Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE14-00290 Temporary Service2/6/20142/6/20142/6/2014 2:52:41 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE14-00289 Temporary Service2/6/20142/6/20142/6/2014 2:33:32 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE14-00288 Temporary Service2/6/20142/6/20142/6/2014 2:17:44 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
ELE14-00242 Conference2/5/20142/6/20142/6/2014 1:26:38 PMADONE
David Phone #: ###-#### Discussed replacing wiring around living room and required receptical layout. Not all walls accessible. Owner will do what he can to comply with layout.
ELE13-03441 Electrical Rough-In2/6/20142/6/20142/6/2014 12:39:52 PMAPASS
Ceiling cover. Danny onsite Phone #: ###-#### >> Inspection requested via web by Buster Bowen Ceiling grid rough in ok cover
ELE14-00018 Electrical Rough-In2/6/20142/6/20142/6/2014 10:10:31 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Mark M Ceiling grid rough in ok cover
ELE13-03022 Final2/5/20142/6/20142/6/2014 10:09:48 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.8- All garage 120 volt 15 and 20 amp recepticals shall have GFCI protection.
406.5- Switches and recepticals shall have faceplates installed.
406.4- Receptical yoke shall be rigidly mounted to box or box cover.
314.20- Boxes set back 1/4" or more shall have spark or extension ring.
ELE13-02929 Final2/5/20142/6/20142/6/2014 9:45:56 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov 210.8- All receptical outlets serving counter top space in kitchen shall have GFCI protection.
210.12- All bedroom outlets shall have AFCI protection. 1 arc won't trip.
Patio lights not working, unable to test for arc protection.
ELE14-00285 Final2/5/20142/6/20142/6/2014 8:52:50 AMACANC
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Needed rough in inspection
ELE14-00285 Rough-In Permanent Service2/6/20142/6/20142/6/2014 8:52:48 AMPPASS
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok
ELE14-00285 Rough-In Permanent Service2/6/20142/6/20142/6/2014 8:52:35 AMPPASS
Phone #: ###-#### >> Inspection requested via web by TOM BICANDI Rough in ok cover p/s u/g n ok